6 Parameter6.5 Parameter descriptionDE1… Variable Speed Starter 11/16 MN040011EN www.eaton.com 109control terminals’ start start and stop commands. However, it will still bepossible to use the two arrow keys on the keypad in order to digitally setthe frequency reference value.6.5.6.5 Analog input (AI1/DI4)By default, control terminal 4 will be configured as analog input AI1(0 - +10 V). The corresponding signal common is terminal 0 V.The signal range for this analog input can be configured using P-16:0 = 0 - 10 V (default settings)1 = 0 - 20 mA2 = 4 - 20 mA (t 4 - 20 mA); if there is a wire breakage, the drive will beswitched off and a fault message will be sent3 = 4 - 20 mA (r 4 - 20 mA); if there is a wire breakage, the drive will usethe set ramp time (P-04) to change the frequency to fixed frequency FF1(P-20; default setting = 20 Hz).P-17 can be used to scale analog input AI1’s input signal.ExampleP-01 = 50 Hz, f-REF = 0 - 10 VP-17 = 1.000: (0 - +10 V) x 1 → 0 - 50 HzAt a reference voltage of 10 V, the output frequency will reachthe value in P-01 (100 %).P-17 = 0.100: (0 - +10 V) x 0.1 → 0 - 5 HzAt 10 V, the output frequency will reach a value of 10 % ofP-01.Note:Higher reference voltages (> 10 V) are not permissible!P-17 = 2.000: (0 - +5 (10) V) x 2 → 0 - 50 (50) HzAt 5 V, the output frequency will reach the value in P-01,and will then remain constant within a range > 5 - 10 V(gain factor: 200 %).P-17 = 2.500: (0 - +4 (10) V) x 2.5 → 0 - 50 (50) Hz,At 4 V, the output frequency will reach the value in P-01,and will then remain constant within a range > 4 - 10 V(gain factor: 250 %).