11 List of parameters166 DE1… Variable Speed Starter 11/16 MN040011EN www.eaton.comP-34 162 RUN rw PDP address 1 - 63 1 PDP addressUnique address of DE1 variable speed starter on acommunication network–P-35 163 RUN rw Modbus Baud rate 0 - 4 4 Modbus Baud rate0 = 960 Bit/s1 = 19.2 kBit/s2 = 38.4 kBit/s3 = 57.6 kBit/s4 = 115.2 kBit/s–P-36 164 RUN rw Modbus RTU COMTimeout0 - 8 0 Modbus RTU, TimeoutIf communication is lost, the device will beswitched off after the specified time elapses:0: Disabled (the device will not be switched off)1: The device will be switched off after 30 ms2: The device will be switched off after 100 ms3: The device will be switched off after 1000 ms4: The device will be switched off after 3000 msStop with deceleration ramp (P-02)5: Stop after 30 ms6: Stop after 100 ms7: Stop after 1000 ms8: Stop after 3000 ms–P-37 165 STOP rw Parameter Set 0; 1 0 Used to restore the device’s default settings0: deactivated1: Activated (will be automatically reset to 0)112P-38 166 RUN rw Password Level 2 0 - 9999 101 PasswordAccess code for the extended parameter set.This code needs to be entered in P-14.111P-39 167 RUN rw Parameter Lock 0; 1 0 Parameter lock0: Not locked. All parameters can be changed.1: Locked. All parameters are locked.Note:Exception P-14, P-20 (FF1).These parameter values can be changed withDXE-EXT-SET even in “locked” mode.111P-40 168 RUN rw Action@Communi-cation Loss0 - 4 0 SWD, communication lossUsed to define how the DE1 variable speed starterwill behave if it loses communication withSmartWire-DT:0: No response (continued operation)1: Alarm message (continued operation)2: STOP function with deceleration time P-04 ifP-05 = 1 (ramp)3: Shutdown (uncontrolled deceleration, free run-down)4: Shutdown with fault messageNote:P-36 can be used to set a delay for the responseto a loss of communication.–PNUModbus IDAccess right Name Value DS DescriptionPageRUN, STOPro/rw