113. Inverter IntroductionEaton Electric General Inverters DF1 Series UMXXXXXXXXE February 2020 www.eaton.com3. Inverter Introduction3.1 General specificationControl method SVPWM control, V/F control, close-loop V/F control (VF+PG), general flux vector control, sensorlessvector control (SVC), close-loop vector control (FOC+PG), torque control (TQC+PG)Output frequency range 0~650.00HzFrequency set-ting resolutionDigital setting The resolution is 0.01HzAnalog setting0.01Hz/60Hz (terminal AI1: -10 ~ +10V / 13bit)0.015Hz/60Hz (terminal AI1: 0 ~ ±10V / 12bit; terminal AI2: 0~10V, 4-20mA / 12bit)0.03Hz/60Hz (terminal AI1, AI2; 0 ~ 5V / 11bit)0.06Hz/60Hz (terminal AI3: 0~10V, 4-20mA / 10bit)0.12Hz/60Hz (terminal AI3: 0 ~ 5V / 9bit)Outputfrequency ac-curacyDigital setting Maximum target frequency ±0.01%Analog setting Maximum target frequency ±0.1%Speed control range IM: WhenSVC, 1:200; when FOC+PG, 1:1000;PM: When SVC,1:20; when FOC+PG, 1:1000Start torque 150% 0.3Hz (SVC),180% 0Hz (FOC+PG)V/Fcharacteristics Constant torque curve, variable torque curve, five-point curve, VF separationAcceleration / deceleration curve char-acteristics Linear acceleration / deceleration curve, S pattern acceleration / deceleration curve 1 & 2 & 3Drive motor Induction motor (IM), permanent magnet motor (SPM, IPM)Stalling protection The stalling protection level can be set to 0~400% (06-01(P.22)). The default value is 150%Target frequency setting Parameter unit setting, DC 0~5V/10V signal, DC -10~+10V signal, DC 4~20 mA signal, multiple speedstage level setting, communication setting, DIH settingPID control Please refer to 08-00~08-01 / 08-04~08-14 / P.170~P.182 in chapter 4Built-in simple PLC Supports 21 basic instructions and 14 application instructions, including PC editing softwareOperationPanelOperation monitoringOutput frequency, output current, output voltage, PN voltage, output torque, electronic thermalaccumulation rate, temperature rising accumulation rate, output power, Analog value input signal,digital input and output terminal status…; alarm history 12 groups at most, the last group of alarmmessage is recordedLED indication lamp(10)Forward rotation indication lamp, reverse rotation indication lamp, frequency monitoring indicationlamp, voltage monitoring indication lamp, current monitoring indication lamp, NET indication lamp, PU-controlindication lamp, EXT indication lamp, PLC indication lamp and MON monitoring indication lampCommunication functionRS-485 communication, can select Eaton/Modbus communication protocol, communication speed-38400bps or below, built-in CanOpenprotocol (DF1-DXF-NET-CAN expanded board can be optional),double RJ-45 connectors (the connector can also be connected to parameter unit)Protection mechanism /alarm functionOutput short circuit protection, Over-current protection, over-voltage protection, under-voltage protec-tion, motor over-heat protection (06-00(P.9)), IGBT module over-heat protection, communication abnor-mality protection, PTC temperature protection etc, electrolytic capacitor overheat, input and outputphase failure, to-earth (ground) leakage currents protection, circuit error detection...