735. Parameter DescriptionEaton Electric General Inverters DF1 Series UMXXXXXXXXE February 2020 www.eaton.com• S pattern acceleration / deceleration curve 3(01-05=“3”)Please refer to 5.2.12 Spattern time setting.Acceleration / deceleration time increments• When 01-08=0, minimum acceleration / deceleration time (01-06、01-07、01-14、01-22、01-23、04-35~04-42)increment is0.01s.• When 01-08=1, minimum acceleration / deceleration time (01-06、01-07、01-14、01-22、01-23、04-35~04-42)increment is 0.1s.Acceleration / deceleration reference frequency• When the output frequency of the inverter is accelerated from 0Hz to01-09, the required time is defined as “accel-eration time”.• When the output frequency of the inverter is decelerated from 0Hz to 01-09, the required time is defined as “decel-eration time”.ote:N 1. S pattern acceleration /deceleration curve 1 is used when acceleration/deceleration is required for a short time until a high-speed area equal to or higher than thebase frequency, such as for the main shaft of the machine.2. S pattern acceleration / deceleration curve 2 can effectively reduce motor vibration during the acceleration / deceleration, andthus prevent the belts and gears from broken.3. S pattern acceleration / deceleration curve 3 is used to start the inverter gradually without impact.4. Please refer to Section 5.2.10 The second function for the second acceleration/deceleration time.5. When RT is “on”, the second function is valid. For the operation characteristics of the motor, please refer to Section 5.2.10.RTmentioned in this section is the function name of the “multi-function digital input terminal”. Please refer to 03-00~03-06, 03-09for function selection and purposes of the multi-function digital input terminal. For related wiring, please refer to Section 3.3.5.2.4 Torque boost V/F• For an inverter controlled by V/F mode, when the motor starts up, the starting torque is usually inadequate since theoutput voltage of the inverter is inadequate. In this case, the output voltage can be elevated by properly setting thetorque boost (01-10), and thus a better starting torque can be acquired.Torque boost• If 01-10=6% and 01-04=220V, and when output frequency of the inverter is 0.2Hz, the output voltage is:• If RT is “on,” “the second torque boost” on 01-24 is valid (Note 2).ote:N 1. If the set value of 01-10 is too high, it will activate current inverter protection or the activation will be impeded.2. Please refer to Section 5.2.10 for the second torque boost.3. RT mentioned in this section is the function name of the “multi-function digital input terminal”. Please refer to 03-00~03-06,03-09 for function selection and purposes of the multi-function digital input terminal. For related wiring, please refer to Section3.3.Parameter Name FactoryValue Setting Range Content01-10P.0 Torque boost6.0%0~30.0%0.75K/1.5KF types4.0% 1.5K/2.2KF~3.7K/5.5KF types3.0% 5.5K/7.5KF~7.5K/11KF types2.0% 11K/15KF~55K/75KF types1.0% 75K/90KF and types aboveVHzHzVPfPPP 03.14%62.050%6%1002200.3.0.%10019. = +×−×= +×−×