15Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comotes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.Table 8. Operate mode—OCode Parameter Min. Max. Unit Default ID NoteO1 Output Frequency Hz 0.00 1O2 Freq Reference Hz 0.00 24O3 Motor Speed rpm 0 2O4 Motor Current A 0.0 3O5 Motor Torque % 0.0 4O6 Motor Power % 0.0 5O7 Motor Voltage V 0.0 6O8 DC-link Voltage V 0 7O9 Unit Temperature °C 0.0 8O10 Motor Temperature % 0.0 9R12 b Keypad Reference See Para ID 101 See Para ID 102 Hz 0.00 141Table 9. Basic parameters—P1Code Parameter Min. Max. Unit Default ID NoteP1.1 ab Min Frequency 0.00 See Para ID 102 Hz 0.00 101P1.2 ab Max Frequency See Para ID 101 400.00 Hz 60.00 102P1.3 b Accel Time 1 0.1 3000.0 s 3.0 103P1.4 b Decel Time 1 0.1 3000.0 s 3.0 104P1.5 a Motor Nom Current Drive NomCT*1/10Drive NomCT*2A Drive Nom CT 486P1.6 a Motor Nom Speed 300 20000 rpm Motor Nom Speed 489P1.7 a Motor PF 0.30 1.00 0.85 490P1.8 a Motor Nom Voltage 180 690 V Motor Nom Voltage 487P1.9 a Motor Nom Frequency 8.00 400.00 Hz Motor Nom Freq 488P1.10 b Power Up Local RemoteSelect0 1685 0 = Hold Last1 = Local Control2 = Remote ControlP1.11 b Remote1 Control Place 0 135 0 = I/O Terminal Start 11 = Fieldbus2 = I/O Terminal Start 23 = KeypadP1.12 b Local Control Place 0 1695 0 = Keypad1 = I/O Terminal Start 12 = I/O Terminal Start 23 = FieldbusP1.13 b Bumpless Enable 0 2464 0 = Disabled1 = Enabled