24Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comotes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.Table 14. Drive control—P7Code Parameter Min. Min. Unit Default ID NoteP7.1 b Remote 2 Control Place 1 138 See Para ID 135P7.2 ab Remote 2 Reference 7 139 See Para ID 136P7.3 b Keypad Reference See Para ID 101 See Para ID 102 Hz 0.00 141P7.4 b Keypad Direction 0 116 0 = Forward1 = ReverseP7.5 b Keypad Stop 1 114 0 = Enabled-Keypad Operation1 = Always EnabledP7.6 b Jog Reference See Para ID 101 See Para ID 102 Hz 0.00 117P7.9 b Start Mode 0 252 0 = Ramp1 = Flying StartP7.10 b Stop Mode 1 253 0 = Coasting1 = RampP7.11 b Ramp 1 Shape 0.0 10.0 s 0.0 247P7.12 b Ramp 2 Shape 0.0 10.0 s 0.0 248P7.13 b Accel Time 2 0.1 3000.0 s 10.0 249P7.14 b Decel Time 2 0.1 3000.0 s 10.0 250P7.15 b Skip F1 Low Limit 0.00 See Para ID 257 Hz 0.00 256P7.16 b Skip F1 High Limit See Para ID 256 400.00 Hz 0.00 257P7.17 b Skip F2 Low Limit 0.00 See Para ID 259 Hz 0.00 258P7.18 b Skip F2 High Limit See Para ID 258 400.00 Hz 0.00 259P7.19 b Skip F3 Low Limit 0.00 See Para ID 261 Hz 0.00 260P7.20 b Skip F3 High Limit See Para ID 260 400.00 Hz 0.00 261P7.21 b Prohibit Accel/Decel Ramp 0.1 10.0 1.0 264P7.22 b Power Loss Function 0 267 0 = Disabled1 = EnabledP7.23 b Power Loss Time 0.3 5.0 s 2.0 268P7.24 b Currency 0 8 $ 2121 0 = $1 = GBP2 = Eur3 = JPY4 = Rs5 = R$6 = Fr7 = KrP7.25 b Energy Cost 0 2122P7.26 b Data Type 0 4 s 0 2123 0 = Cumulative1 = Daily Avg2 = Weekly Avg3 = Monthly AvgP7.27 b Energy Savings Reset 0 1 s 0 2124 0 = No Action1 = ResetP7.28 b 2th Stage Ramp Frequency See Para ID 101 See Para ID 102 Hz 30 2447P7.29 b Change Phase SequenceMotor 0 1 0 2515 0 = Change Disable1 = Change Enable