21Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comotes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.Table 12. Analog output—P4, continuedCode Parameter Min. Max. Unit Default ID Note35 = SlotA PT100 Temp Channel 336 = SlotB PT100 Temp Channel 137 = SlotB PT100 Temp Channel 238 = SlotB PT100 Temp Channel 339 = User Defined Output40 = Motor Current(-2 to +2N)P4.3 b AO1 Minimum 1 149 0 = 0 V / 0 mA1 = 2 V / 4 mAP4.4 b AO1 Filter Time 0.00 10.00 s 1.00 147P4.5 b AO1 Scale 10 1000 % 100 150P4.6 b AO1 Inversion 0 148 0 = Not Inverted1 = InvertedP4.7 b AO1 Offset –100.00 100.00 % 0.00 173P4.8 b AO2 Mode 0 228 See Para ID 227P4.9 b AO2 Function 4 229 See Para ID 146P4.10 b AO2 Minimum 1 232 See Para ID 149P4.11 b AO2 Filter Time 0.00 10.00 s 1.00 230P4.12 b AO2 Scale 10 1000 % 100 233P4.13 b AO2 Inversion 0 231 See Para ID 148P4.14 b AO2 Offset –100.00 100.00 % 0.00 234Table 13. Digital output—P5Code Parameter Min. Min. Unit Default ID NoteP5.1 b DO1 Function 1 151 0 = Not Used1 = Ready2 = Run3 = Fault4 = Fault Invert5 = Warning6 = Reversed7 = At Speed8 = Zero Frequency9 = Freq Limit 1 Superv10 = Freq Limit 2 Superv13 = Overheat Fault14 = Overcurrent Regular15 = Overvoltage Regular16 = Undervoltage Regular17 = 4 mA Ref Fault/Warning20 = Torq Limit Superv21 = Ref Limit Superv22 = Control from I/O23 = Un-Requested RotationDirection24 = Thermistor Fault Output27 = Ext Fault/Warning28 = Remote Control29 = Jog Speed Select30 = Motor Therm Protection31 = FB Digital Input 1