17Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comotes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.Table 10. Analog input—P2Code Parameter Min. Max. Unit Default ID NoteP2.1.1 AI Ref Scale Min Value 0.00 See Para ID 145 Hz 0 144P2.1.2 AI Ref Scale Max Value See Para ID 144 400.00 Hz 0 145P2.2.1 b AI1 Mode 0 1 1 222 0 = 0–20 mA1 = 0–10 VP2.2.2 b AI1 Signal Range 0 2 0 175 0 = 0–100% / 0–20 mA / 0–10 V1 = 20–100% / 4–20 mA / 2–10 V2 = CustomizedP2.2.3 b AI1 Custom Min 0.00 See Para ID 177 % 0.00 176P2.2.4 b AI1 Custom Max See Para ID 176 100.00 % 100.00 177P2.2.5 b AI1 Filter Time 0.00 10.00 s 0.10 174P2.2.6 b AI1 Signal Invert 0 1 0.00 181 0 = Not Inverted1 = InvertedP2.2.7 b AI1 Joystick Hyst 0.00 20.00 % 0.00 178P2.2.8 b AI1 Sleep Limit 0.00 100.00 % 0.00 179P2.2.9 b AI1 Sleep Delay 0.00 320.00 s 0.00 180P2.2.10 b AI1 Joystick Offset –50.00 50.00 % 0.00 133P2.3.1 b AI2 Mode 0 2 1 223 0 = 0–20 mA1 = 0–10 V2 = –10 to +10 VP2.3.2 b AI2 Signal Range 0 2 0 183 0 = 0–100% / 0–20 mA / 0–10 V1 = 20–100% / 4–20 mA / 2–10 V2 = CustomizedP2.3.3 b AI2 Custom Min 0.00 0.00 % 0.00 184P2.3.4 b AI2 Custom Max See Para ID 184 100.00 % 100.00 185P2.3.5 b AI2 Filter Time 0.00 10.00 s 0.10 182P2.3.6 b AI2 Signal Invert 0 1 0.00 189 "0 = Not Inverted1 = Inverted"P2.3.7 b AI2 Joystick Hyst 0.00 20.00 % 0.00 186P2.3.8 b AI2 Sleep Limit 0.00 100.00 % 0.00 187P2.3.9 b AI2 Sleep Delay 0.00 320.00 s 0.00 188P2.3.10 b AI2 Joystick Offset -50.00 50.00 % 0.00 134P2.4.1 b Fine Tuning Input 0 5 0 2484 0 = Not Used1 = AI12 = AI23 = Slot A: AI14 = Slot A: AI15 = FieldbusP2.4.2 b Fine Tuning Min 0.00 100.00 % 0.00 2485P2.4.3 b Fine Tuning Max 0.00 100.00 % 0.00 2486