23Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comTable 13. Digital output—P5, continuedCode Parameter Min. Min. Unit Default ID NoteP5.34 b RO2 On Delay 0 320 s 0 2113P5.35 b RO2 Off Delay 0 320 s 0 2114P5.36 b RO3 On Delay 0 320 s 0 2115P5.37 b RO3 Off Delay 0 320 s 0 2116P5.38 b RO3 Reverse 0 1 0 2117 0 = Not Inverted1 = InvertedP5.39 b Motor Current 1 Supv 0 2189 0 = No Limit1 = Low Limit Superv2 = High Limit SupervP5.40 b Motor Current 1 Supv Value 0 DriveNomCurrCT*2 A DriveNomCurrCT 2190P5.41 b Motor Current 2 Supv 0 2191 0 = No Limit1 = Low Limit Superv2 = High Limit SupervP5.42 b Motor Current 2 Supv Value 0 DriveNomCurrCT*2 A DriveNomCurrCT 2192P5.43 b Second AI Supv Select 0 2193 0 = AI11 = AI2P5.44 b Second AI Limit Supv 0 2194 See Para ID 161P5.45 b Second AI Limit Supv Val 0 100 % 0 2195P5.46 b Motor Current 1 Supv Hyst 0.1 1 A 0.1 2196P5.47 b Motor Current 2 Supv Hyst 0.1 1 A 0.1 2197P5.48 b AI Supv Hyst 1 10 % 1 2198P5.49 b Second AI Supv Hyst 1 10 % 1 2199P5.50 b Freq Limit 1 Supv Hyst 0.1 1 Hz 0.1 2200P5.51 b Freq Limit 2 Supv Hyst 0.1 1 Hz 0.1 2201P5.52 b Torque Limit Supv Hyst 1 5 % 1 2202P5.53 b Ref Limit Supv Hyst 0.1 1 Hz 0.1 2203P5.54 b Temp Limit Supv Hyst 1 10 ? 1 2204P5.55 b Power Limit Supv Hyst 0.1 10 % 0.1 2205otes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.