27Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comTable 16. Protections—P9, continuedCode Parameter Min. Min. Unit Default ID NoteP9.47 b Preheat Temp Source 31 2160 13 = DigIN: A: IO5: 114 = DigIN: A: IO5: 215 = DigIN: A: IO5: 316 = DigIN: A: IO5: 417 = DigIN: A: IO5: 518 = DigIN: A: IO5: 619 = DigIN: B: IO1: 120 = DigIN: B: IO1: 221 = DigIN: B: IO1: 322 = DigIN: B: IO5: 123 = DigIN: B: IO5: 224 = DigIN: B: IO5: 325 = DigIN: B: IO5: 426 = DigIN: B: IO5: 527 = DigIN: B: IO5: 628 = Time Channel 129 = Time Channel 230 = Time Channel 331 = Drive Temperature32 = Slot A PT100 Temp Channel 133 = Slot A PT100 Temp Channel 234 = Slot A PT100 Temp Channel 335 = Slot A Max PT100 Temp36 = Slot B PT100 Temp Channel 137 = Slot B PT100 Temp Channel 238 = Slot B PT100 Temp Channel 339 = Slot B Max PT100 Temp40 = Slot A and Slot B MaxPT100 TempP9.48 b Preheat Enter Temp 0.0 19.9 °C 10.0 2161P9.49 b Preheat Quit Temp 20.0 40.0 °C 20.0 2162P9.50 b Preheat Output Voltage 0.0 20.0 % 2.0 2163P9.56 b STO Fault Response 2 2429 0 = No Action1 = Warning2 = FaultP9.57 b Fault Reset Start 0 1 0 2483 0 = Start/Stop After Fault Reset1 = Restart After Fault ResetTable 17. Preset speed—P12Code Parameter Min. Max. Unit Default ID NoteP12.1 b Preset Speed 1 0.00 See Para ID 102 Hz 5.00 105P12.2 b Preset Speed 2 0.00 See Para ID 102 Hz 10.00 106P12.3 b Preset Speed 3 0.00 See Para ID 102 Hz 15.00 118P12.4 b Preset Speed 4 0.00 See Para ID 102 Hz 20.00 119P12.5 b Preset Speed 5 0.00 See Para ID 102 Hz 25.00 120P12.6 b Preset Speed 6 0.00 See Para ID 102 Hz 30.00 121P12.7 b Preset Speed 7 0.00 See Para ID 102 Hz 35.00 122