20Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comTable 11. Digital input—P3, continuedCode Parameter Min. Max. Unit Default ID NoteP3.54 b Ext. Fault 3 Text 2 2299 0 = External Fault1 = Vibration Cut out2 = High Motor temp3 = Low Pressure4 = High Pressure5 = Low Water6 = Damper Interlock7 = Run Enable8 = Freeze Stat Trip9 = Smoke Detect10 = Seal Leakage11 = Rod BreakageP3.55 b Parameter Set1/2 Sel 0 2312 See Para ID 190P3.56 b Deragging Enable 0 2394 See Para ID 190P3.57 b Off Control 0 2395 See Para ID 190Table 12. Analog output—P4Code Parameter Min. Min. Unit Default ID NoteP4.1 b AO1 Mode 0 227 0 = 0–20 mA1 = 0–10 VP4.2 b AO1 Function 1 146 0 = Not Used1 = Output Frequency2 = Freq Reference3 = Motor Speed4 = Motor Current5 = Motor Torque (0–Nom)6 = Motor Power7 = Motor Voltage8 = DC-Bus Voltage19 = AI120 = AI221 = Output Freq (–2 to +2N)22 = Motor Torque (–2 to +2N)23 = Motor Power (–2 to +2N)24 = PT100 Temperature25 = FB Data Input 126 = FB Data Input 227 = FB Data Input 328 = FB Data Input 429 = FB Data Input 530 = FB Data Input 631 = FB Data Input 732 = FB Data Input 833 = SlotA PT100 Temp Channel 134 = SlotA PT100 Temp Channel 2otes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros. Input function is Level sensed. Input function is Edge sensed. Input function is Edge sensed when using StartP/StopP start logic.