25Step 5 — Standard applicationPOWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.comTable 15. Motor control—P8Code Parameter Min. Min. Unit Default ID NoteP8.1 ab Motor Control Mode 0 287 0 = Freq Control1 = Speed ControlP8.2 a Current Limit Drive NomCT*1/10Drive NomCT*2A Drive Nom VT 107P8.3 ab V/Hz Optimization 0 109 0 = Disabled1 = EnabledP8.4 ab V/Hz Ratio 0 108 0 = Linear1 = Squared2 = Programmable3 = Linear + Flux OptimizationP8.5 ab Field Weakening Point 8.00 400.00 Hz 60.00 289P8.6 ab Voltage at FWP 10.00 200.00 % 100.00 290P8.7 ab V/Hz Mid Frequency 0.00 See Para ID 289 Hz V/Hz Midpoint Freq 291P8.8 ab V/Hz Mid Voltage 0.00 100.00 % 100.00 292P8.9 ab Zero Frequency Voltage 0.00 40.00 % 0.00 293P8.10 b Switching Frequency Min SwitchingFreq Max SwitchingFreq kHz Default SwitchingFreq CT 288P8.11 b Sine Filter Enable 0 1665 0 = Disabled1 = EnabledP8.12 ab Overvoltage Control 1 294 0 = Disabled1 = EnabledP8.17 b Frequency Ramp OutFilterTime Constant 0 3000 ms 0 1585P8.39 b Start Boost Rise Time –1 32000 s 0 1622Table 16. Protections—P9Code Parameter Min. Min. Unit Default ID NoteP9.1 ab 4 mA Input Fault 0 306 0 = No Action1 = Warning2 = Warning: Previous Freq3 = Warning: Preset Freq4 = Fault5 = Fault, CoastP9.2 ab 4 mA Fault Frequency 0.00 See Para ID 102 Hz 0.00 331P9.3 ab External Fault 2 307 See Para ID 313P9.4 ab Input Phase Fault 2 332 See Para ID 313P9.5 ab Uvolt Fault Response 2 330 See Para ID 313P9.6 ab Output Phase Fault 2 308 See Para ID 313P9.7 ab Ground Fault 2 309 See Para ID 313P9.8 ab Motor Thermal Protection 2 310 See Para ID 313P9.9 b Motor Thermal F0 Current 0.0 150.0 % 40.0 311P9.10 b Motor Thermal Time 1 200 min 12 312P9.11 ab Stall Protection 0 313 0 = No Action1 = Warning2 = Fault3 = Fault, CoastP9.12 b Stall Current Limit 0.1 Active MotorNom I*2A Active Motor NomI*13/10314P9.13 b Stall Time Limit 1.0 120.0 s 15.0 315P9.14 b Stall Frequency Limit 1.00 See Para ID 102 Hz 25.00 316P9.15 ab Underload Protection 0 317 See Para ID 313P9.16 b Underload Fnom Torque 10.0 150.0 % 50.0 318otes:N a Parameter value can only be changed after the drive has stopped.b Parameter value will be set to be default when changing macros.