SC200 Handbook30 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.IPN 997-00012-50H November 2011 So that an incorrect Ah Discharged value does not affect cyclic battery charging in a hybridgenerator/battery power system, an incorrect Ah Discharged value will be corrected after onedischarge/recharge cycle:Ah Discharged is set to zero when the recharge reaches Maximum Duration (and thebattery is assumed to be fully charged).Ah Discharged is set to the Start Ah Threshold when the battery discharges down to theVoltage Threshold.Temperature CompensationAs the ambient temperature of a battery drops (or rises) the voltage required to maintain fullcharge increases (or decreases). Temperature Compensation automatically varies the floatvoltage to cancel the effects of changing temperature.Enable Temperature Compensation for optimum battery life and battery capacity over a widertemperature range. Temperature Compensation does NOT function during a Battery Test.► To enable Temperature CompensationUse the SC200 keypad to go to: Control Processes > Temp. Compensation > Enable.Or, in DCTools/Web go to: Control Processes > Temperature Compensation.InformationThe following information is available about Temperature Compensation.Parameter Description Where to find:State Indicates if Temperature Compensation is activeor inactive.SC200: Control Processes >Temp. Compensation >EnableDCTools/Web: ControlProcesses > TemperatureCompensationVoltage Offset The adjustment to the bus voltage being applieddue to the Temperature Compensation. Offset iszero when the battery temperature equals thereference temperature.BatteryTemperatureThe temperature measured by the batterytemperature sensor.SC200: Analogs > BatteryTemperatureDCTools/Web: Batteries