SC200 Handbook46 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.IPN 997-00012-50H November 2011System Alarm ConfigurationThe following system alarm parameters can be configured.Parameter Description Where to find:Severity Set to the required alarm priority. Thisdetermines how the alarm is indicated. Seedetails on page 44.If set to Disabled then the alarm will not activate.SC200: Alarms > AlarmSettings (tab) > SystemAlarm. Select an alarm. Use to scrollto other alarms.DCTools/Web: Alarms >Alarm StatesDO Mapping A If required, select a digital output (relay) thatwill be operated when the alarm is active.DO Mapping B If required, select a second digital output (relay)that will be operated when the alarm is active.Send Trap An SNMP Trap will be sent for this alarm, if SendTrap is True and the alarm's Severity matches thesetting of the SNMP Trap Level (see details onpage 86).Notes Type any required description. When the alarmis active the text will be displayed on the SC200and included in the SNMP trap (if used).The notes can provide instructions about whataction to take when the alarm occurs.Recognition Period The following alarms have individualrecognition periods: AC Fail, System Overload,Generator Fail. All other system alarms either use thestandard Alarm Recognition Period or donot have a recognition period. See detailson page 45. SC200: Alarms > AlarmSettings (tab) > SystemAlarm. Select an alarm. Use to scrollto other alarms.DCTools/Web: Alarms >Alarm ConfigurationHigh or LowThresholdThe following alarms have a high or lowthreshold: High Float, Low Float, High Load,Low Load, Battery Temperature High, BatteryTemperature Low.The alarm will be activated if the measuredvalue is above or below this value, as applicable.Enable High FloatTrackingIf enabled, the High Float alarm threshold willbe increased when the operating voltage isincreased by a voltage control process.Enable Low FloatTrackingIf enabled, the Low Float alarm threshold will bedecreased when the operating voltage isdecreased by a voltage control process.AC AlarmThresholdsUsed in CR48-3G systems, AC Phase 1/2/3 Failand AC Phase 1/2/3 Voltage alarms have %deviation thresholds from the Nominal ACVoltage. For each of these alarms, a commonthreshold applies for all phases.SC200: Alarms > AlarmSettings (tab) > SystemAlarmsDCTools/Web: Alarms >Alarm Configuration > ACAlarm ThresholdsNominal ACVoltageUsed by the AC Phase 1/2/3 Fail and AC Phase1/2/3 Voltage alarms.SC200: Alarms > AlarmSettings (tab)DCTools/Web: Alarms >Alarm Configuration > ACAlarm Thresholds