SC200 Handbook52 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.IPN 997-00012-50H November 2011► To configure the Source(s) for a Smart AlarmConfigure the following parameters for the source(s) for each Smart Alarm. Every Smart Alarm must have at least one Source assigned to it.Alarm SourcesParameter SettingSA Num Type the number (from the Smart Alarm States table) of the Smart Alarm forwhich this source is an input.Status Set to Enabled.Logic Set to either:EQUAL - the Alarm Source will become active when the sourcealarm is Triggered or Active.NOT - the Alarm Source will become active when the source alarmis Inactive.Trigger WhenSource IsSet to either:Triggered - the Alarm Source will become active immediatelywhen the conditions for this alarm become true (or false when Logicis set to NOT). The alarm does not have to be Enabled. Do not use Triggered when Type is set to Smart Alarm.Active - the Alarm Source will become active when the alarmbecomes active (or inactive when Logic is set to NOT), after thealarm recognition time, and only if the alarm is Enabled.Type Set to the appropriate source type: System Alarm, Analog Input High, AnalogInput Low, DI, Smart Alarm.Index Identify the alarm:Source Type = System Alarm:DCTools - type the alarm number from the Alarm States table.Web - select the name of the system alarm from the list.Source Type = AI High/AI Low - type the alarm number from theAnalog Input High Alarms or the Analog Input Low Alarms table.Source Type = DI - type the alarm number from the Digital InputAlarms table.Source Type = Smart Alarm - type the alarm number from the SmartAlarm States table.