SC300 Handbook96 Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.IPN 997-00012-03 B2 Issue B2 July 2018Fan ControllerThe SC300 can manage one FC100 Fan Controller module.The FC100 can control up to 8 fans, with one or two independent proportional control modules.For more information, see FC100 Fan Controller Install and Operation, available from Eaton.The SC300 provides these features when used with the FC100:• Configure primary and secondary control profiles for controller 1 and Controller 2.• Set fan controller mode.• Switch from primary to Secondary control profiles by Smart Alarm control• Manual speed control over-ride.• View temperature inputs• View fan speeds• Report fan controller alarms and values remotely.► To connect a Fan Controller The FC100 fan controller is an RXP device and must be registered with the SC300 before it willcommunicate with it.1 Connect the FC100 communications port (RJ-45) to the RXP bus using an RJ-45 patch cable.. Generally there will be a spare RXP connection on the VFN board.2 In web, go to System > Interfaces > RXP.3 In DCTools, go to Configuration > RXP.4 The RXP Devices table should show the FC100.5 Copy the FC100 serial number into the next available position in the IO Board to SerialNumber Mapping table.6 Click on Apply Changes.► To configure a Control Profile The control profile specifies how fan control power percentage (and hence speed) varies withtemperature. It consists of six temperature / power settings. The FC100 will smoothly increase fan speed astemperature increases from one point to the next. The control profile will be pre-determined according to the enclosure and fan characteristics.Unauthorized changes could cause over-heating.7 Select the required profile to enter. Generally this will be Controller 1, Primary Profile.8 Enter and apply values for all six temperature / power pairs.► To set fan controller modeSet Mode to any of these values:Single Controller All fans are driven from temperature sensor 1 and controller 1 profile.Dual Controller Temperature sensor 1 drives both controllers with their own profiles.Independent Controller The two controllers work independently with their own temperature sensors.