SC300 OperationCopyright © 2007-2018 Eaton Corporation. All Rights Reserved.IPN 997-00012-03 B2 Issue B2 July 2018 15Notes:1 The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current,Battery Temperature, Load Power, System Power, Analog Input, Ah Discharged, Energy Meter, PowerMeter, Current Meter, Smart Analog, Alternative Source Current, Solar Power, Generator Power.2 If Analog Input, Energy Meter, Power Meter, Current Meter, Voltage Meter or Smart Analog isselected as a display parameter, then also select a value for Value 1/2/3 Index. This value is thenumber of the meter or input from the appropriate table.Display Time-outIf there is no keypad activity for 60 seconds the display will go back to the main screen.Alarm IndicatorsVisual indicatorsPower on LED (green)Minor Alarm LED (yellow)Critical/Major Alarm LED (red)??? The system value cannot be displayed because of a failed, disconnected orunconfigured sensor.Audible indicator• One beep – indicates an invalid key press• Three beeps every 2 seconds – refer to the alert message on the display• One beep every 2 seconds – Minor alarm is active• Continuous sound – Critical/Major alarm is active Critical/Major alarms always override Minor alarms.► To stop the audible indicator• Press any key The audible indicator will restart at the next active alarm or alert message.► To enable/disable the audible alarm indicatorEither:• Use the keypad to go to: Alarms > Alarm Settings (tab) > Audible Alarms > Edit.Or:• In Web go to: System > Interfaces> Physical Ports > Front Panel.• In DCTools, go to Configuration > Communications > Front Panel. When Disabled, the audible indicator will still indicate an invalid key press.