SC300 Handbook110 Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.IPN 997-00012-03 B2 Issue B2 July 2018Communication via EmailThe SC300 system controller can be configured to send Email alarm messages when an alarmis activated or de-activated.► To set up Email communications:1 Set up Ethernet communications and connect the SC300 to the IP network. See EthernetCommunications on page 104.2 On the web, go to System > Interfaces > Remote Access Protocols > Email Notifications.3 In DCTools, go to Communications > Remote Access Protocols > Email Notifications.4 Enable Email Notifications.5 Set the following parameters:SMTP Server IP Addressand Port:The details of the mail server that will be used to sendthe Emails.Return Address: If not blank, any delivery failure notifications will besent to this address.Address Use The setting specifies when the address above is used:Address only – the address appears in the From lineUse Address – the return address is shown in theFrom line along with other information.Failure notification only – the address is only used indelivery failure notifications.Subject Prefix: An optional Email subject prefix that will be added toeach Email's subject to allow automatic processing ofthe Email.6 For each Email recipient (up to 6), set the following parameters:Address: The recipient's Email address.Level: The severity of alarms that are to be reported to thisrecipient.• Select Warnings And Above to send an Email whenan alarm with a severity of Warning or abovechanges state.• Select Minor And Above to send an Email when analarm with a severity of Minor or above changesstate.• Select Major And Above to send an Email when analarm with a severity of Major or above changesstate.• Select None to send no Emails.• Select Critical Only to send an Email when analarm with a severity of Critical changes state.Delay: The alarm Email will be delayed by this length oftime. During this delay, the SC300 will collate all theevents that occur into a single Email.