Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01 13Table 4. LCD Operating Modes (Continued)UPS Display DescriptionIN:120V 60.0HZHIGH EFFIC.MODEThe UPS is operating on High Efficiency mode. The UPS ispowering and protecting the equipmentIN:120V 60.0HZBYPASS MODEAn overload or a fault has occurred, or a command has beenreceived, and the UPS is in Bypass mode. Equipment is poweredbut not protected by the UPS.44..33 UUPPSS HHoommee MMeennuuThe SmartOnline UPS will display the Home Menu by default. The Home Menu will display the UPS mode andcontains nine different types of UPS measurements that can be seen by navigating the menu.Navigate the Home Menu by pressing the or buttons on the display.Press the ESC button to return to the first measurement of the Home Menu.Table 5. UPS Home MenuDisplay Information LCD Display Bottom Row ValuesDisplays the UPS mode , load percentageand W.LOAD:100% 2700WONLINE MODEThe LOAD data screen specifies theamount of power that connectedequipment is currently using in terms ofpercentage and Watt.Displays the UPS mode , load percentageand VA.LOAD:100% 3000VAONLINE MODEThe OUTPUT LOAD LEVEL screenindicates the load percentage and VAoutput load level.Displays the UPS mode and output loadpower factor.LOAD:PF=0.99ONLINE MODEThe OUTPUT LOAD POWER FACTORscreen indicates the power factor ofconnected equipment.Displays the UPS mode , input voltageand frequency.IN:120V 60.0HZONLINE MODEThe INPUT VOLTAGE & FREQUENCYscreen displays current UPS input data.Displays the UPS mode and outputvoltage and frequency.OUT:120V 60.0HZONLINE MODEThe OUTPUT VOLTAGE & FREQUENCYscreen displays current UPS output data.Displays the UPS mode , battery voltageand battery charge percentage.BATT:50.2V 100%ONLINE MODEThe BATTERY voltage screen tracks thecharge level of your connected batterybank in terms of voltage and chargepercentage.UPS Home Menu