38 Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01Table 11. UPS Alarm Codes (Continued)Alarm Code Displayed Alarm Potential Cause Action110 BUILDING ALARM building alarm by input signalcontactor200 BP PHASE NOT OKPhase out of range (bypassinput and inverter outputcannot phase lock)Check Bypass AC frequency206 BP FREQ. NOT OK Frequency out of range Check Bypass AC frequency208 BP OVERLOAD Bypass overload alarm Check and reduce load209 BP VOLT NOT OK Input Voltage out of bypassrange Please check input voltage603 BATTERY MODE Battery is discharging Please check input voltage604 BATTERY LOWBattery level is belowRemainingCapacityLimitthreshold or RunTimetoEmptyis below RemainingTimeLimitthreshold.Please check the mains and Prepare toshut off load60D NO BATTERY Battery not present Please check if batteries are connectedrightly or fuse is open612 BAT TEST ABORTED Battery test condition is notmet.Check: UPS mode is AC (online) or HE;Load must be greater than 10%;Battery capacity should be >=80%;There is no running alarm (exceptedBattery fault);Load level has not varied by more than+/- 10 percent (from the initial load levelpresent at the beginning of the test tothe beginning of step2 test).700 CURRENT LIMIT inverter current limitation Check load706 UPS TEMP. ALARM UPS internal temperature ishighPlease check ambient temperature and ifthe ventilation is blocked, and if fanworks normal.802 IMMINENT SHUTOFF shut down imminent forbattery low Please prepare for shutdown806 EMERGENCY OFF emergency stop was proceed Please check if RPO is active80E OVLD PREALARMoutput power above threshold102%(default), settable fromHMI.Check overload pre-alarm setting andload810 POWER OVERLOAD Output power overload, Max(P,S) > L2 (L2 = 102%) Please check the load capacityTypical Alarms and Faults