Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01 43Table 17. Electrical output (Continued)Nominal output 100 / 110 / 120 / 125 (for 120V models)Frequency 50 or 60Hz. autosensing or configurable as a frequency converterOutput overload(Online Mode)102%~130%* 12 seconds130%~150%* 2 seconds>150%* Shutdown immediately**Output overload(Battery Mode)102%~130%* 12 seconds130%~150%* 2 seconds>150%* Shutdown immediately, overload warning **Output overload(Bypass Mode)102%~110%* Overload warning110%~130%* Shutdown after 5 minutes130%~150%* Shutdown after 15 seconds>150%* Shutdown after 300 msVoltage waveform Sine waveHarmonic distortion < 3% THDV on linear load< 5% THDV on non-linear loadTransfer time Online mode: 0 msHigh Efficiency mode: 10 ms maximum (due to loss of utility)Power factor Up to 0.9Load crest ratio Up to 3:1* Percent is based on nominal Watt/VA** Behaviour can change (see output mode in In/Out settings)Table 18. Electrical Output ConnectionsCatalog Number (UPS) Output Connection Output CableSU700XLCD (2) NEMA 5–15R(2) NEMA 5–15R Group1(2) NEMA 5–15R Group2NASU1000XLCDSU1500XLCDSU2200XLCD(2) NEMA 5–20R Primary(2) NEMA 5–20R + (1) NEMA L5–20RGroup 1(2) NEMA 5–20R Group2 NASU3000XLCD(1) NEMA L5–30R Primary(2) NEMA 5–20R Group1(2) NEMA 5–20R Group2Model Specifications