44 Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01Table 19. Environmental and SafetyCertificationsIEC/EN 62040-1IEC/EN 62040-2 : Cat. C2IEC/EN 62040-3UL1778 5th editionCSA 22.2EMC EN IEC 62040–2: C2FCC part 15 Class A/ ICES-003 (A)Agency MarkingscTUVus/NOM(TUV NOM)/CE (SU700XLCD — SU1500XLCDModels)cTUVus/NOM(TUV NOM)/CE (SU2200XLCD — SU3000XLCDModels)CE/cTUVus (BP36–BP96V Models)Protective Class IOutput short-circuit current max RMS & delay time 59.2A / 7 cycles; The max peak value: 90AThis UPS can be used in and supplied to load TN power system.UPS enclosure IP rating IP20Operating Temperatures0 to 40 °C (32 to 104 °F) in Online mode, with linear deratingfor altitudeNote: thermal protection switches load to Bypass in case ofoverheating.Storage Temperatures 0 to 40°C (32 to 104°F) with batteries-25 to 55°C (-13 to 130°F) without batteriesTransit Temperature -25 to 55°C (-13 to 130°F)Relative Humidity 0 to 96% no condensingOperating Altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for35°c (95°F) room temperatureTransit Altitude Up to 10,000 meters (32,808 ft) above sea levelAudible Noise < 50 dBA at 1 meter typicalTable 20. BatteryInternal Batteries EBMTower configuration700VA: 24Vdc1000VA: 48Vdc1500VA: 48Vdc2200VA: 96Vdc3000VA: 96VdcBP36V: 36Vdc- 2 x 3 x 12V. 9AhBP48V: 48Vdc- 2 x 4 x 12V. 9AhBP96V: 96Vdc- 2 x 8 x 12V. 9AhType Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year floatservice life at 25 °C (77 °F). Lifetime is reduced above 25°C (77°F)EBM Battery Cable Length 400 mm / 15.75 inModel Specifications