Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01 271. From the “UPS Home Menu“ press the button to enter into the “Main Menu Screen”.2. In the “Main Menu Screen” press the or button until the “IN / OUT SETTINGS” menu is displayed.3. Press the button. Use the or arrow buttons to display “HIGH EFFIC. MODE”.4. Press the button and change the setting to “ENABLED”.5. The UPS transfers to High Efficiency mode after 5 minutes.55..77 CCoonnffiigguurriinngg tthhee BBaatttteerryy SSeettttiinnggssLow battery warningDuring discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less thanthe setting capacity threshold (0 % by default). This threshold can be modified.Restart battery levelThis setting is used to define the battery restart level. The battery level must reach this threshold (0 % bydefault) to enable UPS start.See the 4.5 User Settings section to modify these settings.55..88 RReettrriieevviinngg tthhee EEvveenntt LLooggTo retrieve the Event log through the display:1. From the “4.3 UPS Home Menu“ press the button to enter into the “4.5 User Settings”.2. In the “4.5 User Settings” press the or button until the “Event Log” menu is displayed.3. Press the button. Use the or arrow buttons to display the events.The log retains 50 events with the most recent event listed as the first event. Press the ESC button twice toexit back to the “4.3 UPS Home Menu” menu .Configuring the Battery Settings