1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I III-512530/12540 OPERATING INSTRUCTIONSAlarm OperationIn case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the panel buzzersounds. Local audible and visual signals and remote alarm signals operate.When an alarm occurs, proceed according to the established emergency plan. Assure that all personnelare accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automaticsignal has been received at the Fire Department.Authorized Personnel OnlyTo silence the alarm:To silence the notification appliances after evacuation, where permitted, operate the ButtonEnable keyswitch and press the Alarm Silence switch. The notification appliances and panelbuzzer will be silenced, and LED indications will change from flashing to continuous. The AlarmSilenced LED will be lit.Note: Do not reset the panel until the alarm has been cleared.Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for apredetermined time.To reset panel after alarm:When the alarm condition is corrected, return the panel to normal standby operation by operatingthe Button Enable keyswitch pressing the System Reset switch.Trouble OperationTrouble is indicated by:System Trouble LED flashesLCD will display trouble conditionsPanel buzzer soundsTo silence the trouble buzzer:Operate the Button Enable keyswitch and press the Trouble Silence switch. The TroubleSilenced LED lights and the specific trouble LED(s) may change to continuous display. When thetrouble condition has been cleared, you may need to reset the panel to restore to a normalstandby condition.Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not toinitiate a fire alarm sequenceNormal Standby ConditionThe green AC Power On LED will be lit and no other indicators on.For service, contact: ___________________________________________Telephone Number: ___________________________________________Frame these instructions and mount them near the control unit for operator reference.