1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I V-2WIRING SEPARATIONAll high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼”separation must be maintained, with high voltage and non-power limited wiring running in separateconduit openings from power limited wiring.ECAB HFA. Non-power limited - High Voltage(AC power) or BB. Non-power limited - High Voltage(AC power) or AC. Power limited (or E or F or H)D. Non-power limited(Battery If external enclosure required)E. Power limited (or C or F or H)F. Power limited (or C or E or H)G. Non-power limited(Local Energy or Shunt City Tie)H. Power limited (or C or E or F)D G1. Main Termination Board2. 12522 Loop Driver Board3. 12401A Class A Adapter4. 12503 Conventional Expansion Board5. 12505 Loop/Signal Expansion6. 12504 Class A Adapter7. 12402 Relay Board8. 12511 Serial Isolation Board9. 12513 DACT Expansion Module