1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I IX-5UL Compatible Two-Wire (Circuit Powered) Smoke & Heat DetectorsZone Identifier – H for 12503 Conventional Expansion BoardFaradayDetectorw/BaseMfg.Detectorw/BaseNumber ofDetectorsPer CircuitMaximumStandbyCurrentDetectorIdentifierBaseIdentifierAir Products & Controls9267 RW-2W-N 0-30 0.081mA RW-2WN 45681-2009268 RW-2W-P 0-27 0.110mA RW-2WP 45681-200Apollo Fire Detectors9260 w/9262 55000-350 w/45681-220 0-27 0.110mA 55000-350 45681-2209260 w/9265 55000-350 w/45681-230 0-23 0.130mA 55000-350 45681-2309261 w/9262 55000-250 w/45681-220 0-30 0.081mA 55000-250 45681-2209261 w/9265 55000-250 w/45681-230 0-30 0.100mA 55000-250 45681-2309264 w/9262 55000-153 w/45681-220 0-30 0.057mA 55000-153 45681-2209264 w/9265 55000-153 w/45681-230 0-30 0.057mA 55000-153 45681-2309274 w/9262 55000-152 w/45681-220 0-30 0.057mA 55000-152 45681-2209274 w/9265 55000-152 w/45681-230 0-30 0.089mA 55000-152 45681-230Faraday, LLC8842 w/8853 8842 w/8853 0-27 0.110mA 8842 88538842 w/8853 (5) 8842 w/8853 (5) 0-13 0.220mA 8842 88538843 w/8853 8843 w/8853 0-27 0.110mA 8843 88538843 w/8853 (5) 8843 w/8853 (5) 0-13 0.220mA 8843 88538854 w/8853 8854 w/8853 0-27 0.110mA 8854 88538854 w/8853 (5) 8854 w/8853 (5) 0-13 0.220mA 8854 88538854 w/8840 8854 w/8840 0-27 0.110mA 8854 88408854 w/8840 (5) 8854 w/8840 (5) 0-13 0.220mA 8854 8840System Sensor9184 w/9185 1151 w/B110LP 0-25 0.120mA A A9183 w/9185 2151 w/B110LP 0-25 0.120mA A A8434 2100S 0-25 0.120mA A ---8415 2100TS 0-25 0.120mA A ---8423 DH100P 0-25 0.120mA A ---9374 1400 0-25 0.120mA A ---9375 2400 0-25 0.120mA A ---9376 2400TH 0-25 0.120mA A ---9358 w/9361 1451 w/B401B 0-25 0.120mA A A9358 w/9364 1451 w/B401 0-25 0.110mA A A9359 w/9361 2451 w/B401B 0-25 0.120mA A A9359 w/9364 2451 w/B401 0-25 0.120mA A A9360 w/9361 2451TH w/B401B 0-25 0.120mA A A9360 w/9364 2451TH w/B401 0-25 0.120mA A A9447 w/9361 5451 w/B401B 0-25 0.120mA A A9447 w/9364 5451 w/B401 0-25 0.120mA A A9176 DH400I (1451DH w/DH400) 0-25 0.120mA A A9177 DH400P (2451 w/DH400) 0-25 0.120mA A ANotes:1. These detector models may be mixed and matched as long as the total maximum standby currentdoes not exceed 3.0 mA per initiating device circuit. The total number of detectors on a circuitshould not exceed 30.2. This control unit is not intended to handle more than one 2-wire detector in alarm, per circuit.3. The activation of a manual pull station or any other contact device, will prevent any 2-wiredetector on the same circuit from remaining activated or activating.4. If the smoke detector has an alarm verify function, the circuit must not be programmed for alarmverify.5. When these detectors are used with 8844 or 8848 Remote LED, the standby current is doubled.6. For specific wiring and installation information, read the instructions provided with each device.