1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I IX-6UL Compatible Four-Wire (Separately Powered) Smoke DetectorsFaradayDetectorw/BaseMfg. Detector w/Base MaximumStandbyCurrentMaximumAlarm CurrentNotesAir Products & Controls9269 RW-DC-N 0.081mA 115mA Must use EOL Relay9270 RW-DC-P 0.110mA 115mA Must use EOL RelayApollo Fire Detectors9221 w/9266 55000-380 w/45681-227 0.205mA 100mA Must use EOL Relay9222 w/9266 55000-150 w/45681-227 0.086mA 100mA Must use EOL Relay9259 w/9266 55000-151 w/45681-227 0.086mA 100mA Must use EOL Relay9260 w/9266 55000-350 w/45681-227 0.130mA 100mA Must use EOL Relay9261 w/9266 55000-250 w/45681-227 0.081mA 100mA Must use EOL Relay9264 w/9266 55000-153 w/45681-227 0.086mA 100mA Must use EOL Relay9274 w/9266 55000-152 w/45681-227 0.096mA 100mA Must use EOL RelaySystem Sensor8416 2124S 0.050mA 25mA Must use EOL Relay8417 2124TS 0.050mA 25mA Must use EOL Relay8418 2124R 0.050mA 45mA Must use EOL Relay8419 2124TR 0.050mA 45mA Must use EOL Relay8420 2124AT 0.050mA 65mA Must use EOL Relay8421 2124ATR 0.050mA 65mA Must use EOL Relay8422 2124AITR 0.050mA 65mA Must use EOL Relay9175 6424 20mA 38.4mA Must use EOL Relay & six wires9184 w/9186 1151 w/B112LP 0.120mA 36mA Must use EOL Relay9183 w/9186 2151 w/B112LP 0.120mA 36mA Must use EOL Relay9338 2124 0.050mA 25mA Must use EOL Relay9339 2124T 0.050mA 25mA Must use EOL Relay9340 2124TSRB 15mA 45mA Must use EOL Relay9358 w/9362 1451 w/B402B 0.120mA 36mA Must use EOL Relay9359 w/9362 2451 w/B402B 0.120mA 36mA Must use EOL Relay9360 w/9362 2451TH w/B402B 0.120mA 36mA Must use EOL RelayNotes:1. For specific wiring and installation information, read the instructions provided with each device.2. Each 9273 EOL Relay requires 15 mA. standby current.