1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I X-2B. System TroublesENTRY INDICATESAC Trouble AC input low or offAddrLp l DBLSHT Double short trouble on addressable loop lAddrLp l OPEN Open circuit trouble on addressable loop lAddrLp l SHORT Short circuit trouble on addressable loop lAUX POWER Trb Auxiliary power monitor input troubleAXLP Bad Msg Main processor to loop processor communication troubleAXLP Fifo Xmit Main processor to loop processor communication troubleAXLP NoRespons Main processor to loop processor communication troubleBATT Trouble Battery input low or offCITY Trouble Local Energy circuit openCM1aa NoRespons Programmed control module not responding on loop 1 at address aaCM1aa DataError More than one device responding on loop 1 at address aaCM1aa OPEN Control module NAC wiring open on loop 1 at address aaCM1aa SHORT Control module NAC wiring shorted on loop 1 at address aaDACT Trouble DACT troubleDACT Acct Trb DACT account reporting troubleDACT Com Trouble DACT communication trouble with main processorDACT PL x Trouble Open or short on DACT phone line xFLASH FATAL Trb Configuration Flash memory troubleGRND FAULT Trb Ground Fault troubleIDCxx Trouble IDC xx wiring is openLCDxx NoRespons LCD Annunciator xx programmed but is not respondingLCDxx Not Pgmd LCD Annunciator xx is not programmed but is respondingLCDxx Trouble LCD Annunciator xx reports troubleMD100 Addr=00 Module on loop 1 responded to address 00MD1aa Not Pgmd Module responding is not programmed on loop 1 address aaMM1aa NoRespons Programmed monitor module not respondingMM1aa DataError More than one device responding on loop 1 at address aaMM1aa Bad PWs Module responses are not valid on loop 1 address aaMM1aa Bad Pgm Module responding is not the type programmed on loop 1 address aaMM1aa OPEN Module IDC wiring open on loop 1 address aaMNLP Bad Msg Main processor to loop processor communication troubleMNLP Fifo Xmit Main processor to loop processor communication troubleMNLP NoRespons Main processor to loop processor communication troubleNACxx Trouble NAC xx wiring is open or shortedPC Pgmr Trb Control unit is not receiving communication from PCPrinter Error Printer is off-line or out of paperQuickTest Abort Quick Test Timer expired causing abnormal exit of Quick TestSNl00 Addr=00 Sensor on loop l responded to address 00SNlaa DataError More than one sensor responding on loop l at address aaSNlaa NoRespons Programmed sensor not responding on loop l address aaSNlaa Bad PWs Sensor responses are not valid on loop l address aaSNlaa Tst Flt Sensor is not entering or exiting test mode on loop l address aaSNlaa Bad Pgm Sensor responding is not the type programmed on loop l address aaSNlaa TRBL Sensor needs maintenance on loop l address aaSNlaa Not Pgmd Sensor responding is not programmed on loop l address aaSNlaa MaintAlrt Sensor needs cleaning on loop l address aaSNlaa TestValue Not receiving valid sensor test reading on loop l address aaTrb Reminder Trouble Reminder timer expired