1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I V-3PRIMARY AND SECONDARY POWER WIRINGThe AC main connections and the battery connections must be made along the left-hand side of theboard. Route all high voltage and non-power limited wiring together and away from power limited wiring.PRINTER WIRINGThe printer connections must be made along the right-hand side of the board. The RS232 outputprovides event data for connection to a printer, terminal or computer.Faraday RPR-100DIP Switch SettingsControl Board Serial BoardSwitch Bank 1Serial BoardSwitch Bank 2SW-1 ON-Language (Unlashed 0) ON-Odd Parity ON-4800 bpsSW-2 OFF-Language (Unlashed 0) ON-No Parity OFF-4800 bpsSW-3 OFF-Language (Unlashed 0) ON-8 Bit Data ON-4800 bpsSW-4 OFF-Form Length (11”) ON-Ready/Busy OFF-DSR InactiveSW-5 ON-Form Length (11”) ON-Diagnostic-Circuit Test ON-Buffer Threshold (32 bytes)SW-6 ON-Auto Line Feed (ON) ON-Normal Print Mode OFF-Busy Signal Timing (1S)SW-7 ON-Data Bits (8) ON-DTR ON-DTR Signal (space after power on)SW-8 ON-Front Panel (Disable) ON-DTR OFF-Not Used24V Battery Set(7 to 38AH)SupervisedNon-Power Limited120VAC/240VAC 50/60Hz3A/1.5A max., SupervisedNon-Power LimitedACNGNDKeep All Non-Power Limited WiringSeparate from Power Limited WiringB+B-Control unitFunctionPrinterFunctionPrinter orTerminalPrinter orTerminalComputerMale9-PinMale25-PinFemale9-PinCTS DTR 8 20 4TXD RXD 2 3 2RXD TXD 3 2 3GND GND 5 7 5Settings: 4800 bps, 8 data bits, 1 stop bit, no parity