1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A LP/N 447203 Issue I VI-1VI. PROGRAMMING THE CONTROL UNITMAIN TERMINATION BOARD JUMPERSFactory setting is shown.P12 – Processor Failure Relay Contact Type• DGRDO (Open – Form A)•• DGRDC (Closed – Form BP13 – External Power Monitor• On = Disabled• Off = EnabledP50 – Addressable Device Circuit #1 Wiring Style• Style 4•• Style 6/7P51 – Addressable Device Circuit #2 Wiring Style• Style 4•• Style 6/7P52 – Reverse Polarity Supervision• Remote•• LocalCity Tie Selection Jumper Plug (Move the jumper plug to the desired type of city tie)JP1 - Reverse PolarityJP2 – Local EnergyJP3 – Shunt