ASTAT XL User Manual Fout! Stijl niet gedefinieerd.24 DET-8126.1.5 Inside delta installation, internally bypassedM36/T32/T113144/T2K1U1(1) U2(4)V1(2) V2(5)W1(3) W2(6)5/L33/L21/L1EK1 F1K1 Main contactor (stronglyrecommended)F1 Semiconductor fuses(optional)CAUTIONWhen connecting the ASTAT XL in inside delta configuration, always install a main contactor orshunt trip circuit breaker.6.1.6 Inside delta installation, externally bypassedNon-bypassed models have dedicated bypass terminals, which allow the ASTAT XL to continueproviding protection and monitoring functions even when bypassed via an external bypass contactor.The bypass contactor must be connected to the bypass terminals and controlled by a programmableoutput configured to Run (see parameters 7A~7I).M36/T32/T15/L33/L21/L113144/T2EK1K1 F1U1(1) U2(4)V1(2) V2(5)W1(3) W2(6)L2B*L1B*L3B*K22421K2 K1 Main contactor (stronglyrecommended)K2 Bypass contactor(external)F1 Semiconductor fuses(optional)NOTEThe bypass terminals on QLxxX0255D are T1B, T2B, T3B. The bypass terminals onQLxxX0360D ~ QLxxX1600D are L1B, L2B, L3B.The fuses can be installed on the input side if required.CAUTIONWhen connecting the ASTAT XL in inside delta configuration, always install a main contactor orshunt trip circuit breaker.