ASTAT XL User Manual Fout! Stijl niet gedefinieerd.DET-812 35To activate jog operation, use a programmable input (parameter 6D). If any other command isreceived when jogging the starter will stop and await a new command.NOTESoft start and soft stop are not available during jog operation.Jog is only available for the primary motor.CAUTIONSlow speed running is not intended for continuous operation due to reduced motor cooling.Jog operation causes the motor to heat faster than the rate calculated by the motor thermalmodel. If you are using jog, install a motor thermistor or allow sufficient restart delay(parameter 5A)7.8 Inside Delta OperationAdaptive Control, Jog, Brake and PowerThrough functions are not supported with inside delta (six-wire)operation. If these functions are programmed when the starter is connected inside delta thebehaviour is as given below:Adaptive Control Start The starter performs a constant current start.Adaptive Control Stop The starter performs a TVR soft stop if parameter 2I Stop Time is >0 secs. Ifparameter 2I is set to 0 secs the starter performs a coast to stop.Jog The starter issues a warning with the error message Unsupported Option.Brake The starter performs a coast to stop.PowerThrough The starter trips with the error message Lx-Tx Shorted.NOTEWhen connected in inside delta, current imbalance is the only phase loss protection that isactive during run. Do not disable current imbalance protection (parameter 4A) during insidedelta operation.CAUTIONInside delta operation is only possible with mains voltage ≤ 600 VAC.