ASTAT XL User Manual Fout! Stijl niet gedefinieerd.36 DET-8128 Programming MenuThe Programming Menu lets you view and change programmable parameters that control how theASTAT XL operates.To open the Programming Menu, press the MENU/ENTER button while viewing the status or graphscreens.To navigate through the Programming Menu:• to scroll through parameter groups, press the or button.• to open a submenu, press the ENTER button.• to view the parameters in a group, press the ENTER button.• to return to the previous level, press the EXIT button.• to close the Programming Menu, press EXIT repeatedly or press the STATUS or GRAPHS button.To change a parameter value:• scroll to the appropriate parameter in the Programming Menu and press ENTER to enter editmode.• to alter the parameter setting, use the and buttons. Pressing or once willincrease or decrease the value by one unit. If the button is held for longer than five seconds, thevalue will increase or decrease at a faster rate.• to save changes, press ENTER. The setting shown on the display will be saved and the keypadwill return to the parameter list.• to cancel changes, press EXIT. The keypad will ask for confirmation, then return to the parameterlist without saving changes.You can access the Programming Menu at any time, including while the soft starter is running. Anychanges to the start profile take effect immediately.The Programming Menu contains four sub-menus:Quick Setup Menu Provides access to quick setup options for common applications.Standard Menu The Standard Menu provides access to commonly used parameters, allowingyou to configure the ASTAT XL to suit your application.Extended Menu The Extended Menu provides access to all the ASTAT XL's programmableparameters, allowing experienced users to take advantage of advancedfeatures.Setup Tools Setup Tools includes maintenance options to configure the ASTAT XL's dateand time or load a standard parameter set.8.1 Quick SetupThe Quick Setup Menu makes it easy to configure the ASTAT XL for common applications. The ASTAT XLselects the parameters relevant to the application and suggests a typical setting, and you can adjusteach parameter to suit your exact requirements.Always set parameter 1A Motor Full Load Current to match the motor's nameplate full load current.The suggested value is the starter's minimum full load current.On the display, the highlighted values are suggested values and the values enclosed in a box are theloaded values.