GE Multilin B30 Bus Differential System 5-75 SETTINGS 5.1 OVERVIEW5The UR platform allows for a maximum of three sets of three-phase voltages and six sets of three-phase currents. Theresult of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number ofsources is six. A summary of CT/VT module configurations is shown below.c) CT/VT INPUT CHANNEL CONFIGURATIONUpon relay startup, configuration settings for every bank of current or voltage input channels in the relay are automaticallygenerated from the order code. Within each bank, a channel identification label is automatically assigned to each bank ofchannels in a given product. The bank naming convention is based on the physical location of the channels, required by theuser to know how to connect the relay to external circuits. Bank identification consists of the letter designation of the slot inwhich the CT/VT module is mounted as the first character, followed by numbers indicating the channel, either 1 or 5. Seethe HardFiber instruction manual for designations of HardFiber voltage and current banks.For three-phase channel sets, the number of the lowest numbered channel identifies the set. For example, F1 representsthe three-phase channel set of F1/F2/F3, where F is the slot letter and 1 is the first channel of the set of three channels.Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display themin the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1,F5, M1, M5, U1, and U5.ITEM MAXIMUM NUMBERCT/VT Module 3CT Bank (3 phase channels, 1 ground channel) 6VT Bank (3 phase channels, 1 auxiliary channel) 3