GE Multilin B30 Bus Differential System 5-355 SETTINGS 5.2 PRODUCT SETUP5This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point statusvalue, its associated quality flags, and a floating point analog value.The following procedure illustrates the transmission configuration.1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGURABLEGOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu:– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.– Set ITEM 3 to “MMXU1.MX.Hz.mag.f” to indicate the analog frequency magnitude for MMXU1 (the metered fre-quency for SRC1).The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analogvalue. The reception dataset on the receiving device must exactly match this structure.2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU-RABLE GOOSE 1 settings menu:– Set CONFIG GSE 1 FUNCTION to “Enabled”.– Set CONFIG GSE 1 ID to an appropriate descriptive string (the default value is “GOOSEOut_1”).– Set CONFIG GSE 1 DST MAC to a multicast address (for example, 01 00 00 12 34 56).– Set the CONFIG GSE 1 VLAN PRIORITY; the default value of “4” is OK for this example.– Set the CONFIG GSE 1 VLAN ID value; the default value is “0”, but some switches may require this value to be “1”.– Set the CONFIG GSE 1 ETYPE APPID value. This setting represents the ETHERTYPE application ID and must matchthe configuration on the receiver (the default value is “0”).– Set the CONFIG GSE 1 CONFREV value. This value changes automatically as described in IEC 61850 part 7-2. Forthis example it can be left at its default value.3. Configure the data by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTO-COL GGIO1 STATUS CONFIGURATION settings menu:– Set GGIO1 INDICATION 1 to a FlexLogic operand used to provide the status of GGIO1.ST.Ind1.stVal (for example, acontact input, virtual input, a protection element status, etc.).4. Configure the MMXU1 Hz Deadband by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTOCOL MMXU DEADBANDS MMXU1 DEADBANDS settings menu:– Set MMXU1 HZ DEADBAND to “0.050%”. This will result in an update to the MMXU1.MX.mag.f analog value with achange greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency.The B30 must be rebooted (control power removed and re-applied) before these settings take effect.The following procedure illustrates the reception configuration.1. Configure the reception dataset by making the following changes in the PRODUCT SETUP COMMUNICATION IEC61850 PROTOCOL GSSE/GOOSE CONFIGURATION RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE1 CONFIG GSE 1 DATASET ITEMS settings menu:– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.– Set ITEM 3 to “GGIO3.MX.AnIn1.mag.f” to indicate the analog magnitude for GGIO3 analog input 1.The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analogvalue. This matches the transmission dataset configuration above.2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS REMOTE DEVICES REMOTE DEVICE 1 settings menu:– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.