5-30 B30 Bus Differential System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT / MME POINTSUp to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for thefull range of assignable parameters.The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the B30 is restarted.i) IEC 61850 PROTOCOLPATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOLThe B30 Bus Differential System is provided with optional IEC 61850 communications capability. This fea-ture is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 foradditional details. ANALOG INPUT / MME POINTSPoint: 0OffRange: any FlexAnalog parameterMESSAGE Point: 1OffRange: any FlexAnalog parameter↓MESSAGE Point: 255OffRange: any FlexAnalog parameter IEC 61850 PROTOCOL GSSE / GOOSE CONFIGURATIONMESSAGE SERVER CONFIGURATIONMESSAGE IEC 61850 LOGICAL NODE NAME PREFIXESMESSAGE MMXU DEADBANDSMESSAGE GGIO1 STATUS CONFIGURATIONMESSAGE GGIO2 CONTROL CONFIGURATIONMESSAGE GGIO4 ANALOG CONFIGURATIONMESSAGE GGIO5 UINTEGER CONFIGURATIONMESSAGE REPORT CONTROL CONFIGURATIONMESSAGE XCBR CONFIGURATIONMESSAGE XSWI CONFIGURATIONNOTENOTE