GE Multilin B30 Bus Differential System 5-1395 SETTINGS 5.6 GROUPED ELEMENTS5Figure 5–56: GROUND IOC1 SCHEME LOGIC5.6.7 BREAKER FAILUREPATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) BREAKER FAILURE BREAKER FAILURE 1(6) BREAKER FAILURE 1BF1 FUNCTION:DisabledRange: Disabled, EnabledMESSAGE BF1 MODE:3-PoleRange: 3-Pole, 1-PoleMESSAGE BF1 SOURCE:SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6MESSAGE BF1 USE AMP SUPV:YesRange: Yes, NoMESSAGE BF1 USE SEAL-IN:YesRange: Yes, NoMESSAGE BF1 3-POLE INITIATE:OffRange: FlexLogic operandMESSAGE BF1 BLOCK:OffRange: FlexLogic operandMESSAGE BF1 PH AMP SUPVPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 N AMP SUPVPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 USE TIMER 1:YesRange: Yes, NoMESSAGE BF1 TIMER 1 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 2:YesRange: Yes, NoMESSAGE BF1 TIMER 2 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 3:YesRange: Yes, NoMESSAGE BF1 TIMER 3 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001SETTINGGROUND IOC1FUNCTION:Disabled = 0Enabled = 1SETTINGGROUND IOC1SOURCE:IGGROUND IOC1BLOCK:Off = 0FLEXLOGIC OPERANDSGROUND IOIC DPOGROUND IOC1 OPSETTINGSETTINGIG ≥ PICKUPGROUND IOC1PICKUP:RUNGROUND IOC1 PICKUPDELAY:SETTINGSGROUND IOC1 RESETDELAY:tPKPtRST827037A4.VSDANDGROUND IOC1 PKP