GE Multilin B30 Bus Differential System 5-415 SETTINGS 5.2 PRODUCT SETUP5The measured value settings for each of the 32 analog values are shown below.PATH: SETTINGS PRODUCT... COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATION GGIO4 ANALOG 1(32) MEASURED VALUEThese settings are configured as follows.• ANALOG IN 1 VALUE: This setting selects the FlexAnalog value to drive the instantaneous value of each GGIO4 ana-log status value (GGIO4.MX.AnIn1.instMag.f).• ANALOG IN 1 DB: This setting specifies the deadband for each analog value. Refer to IEC 61850-7-1 and 61850-7-3for details. The deadband is used to determine when to update the deadbanded magnitude from the instantaneousmagnitude. The deadband is a percentage of the difference between the maximum and minimum values.• ANALOG IN 1 MIN: This setting specifies the minimum value for each analog value. Refer to IEC 61850-7-1 and61850-7-3 for details. This minimum value is used to determine the deadband. The deadband is used in the determina-tion of the deadbanded magnitude from the instantaneous magnitude.• ANALOG IN 1 MAX: This setting defines the maximum value for each analog value. Refer to IEC 61850-7-1 and61850-7-3 for details. This maximum value is used to determine the deadband. The deadband is used in the determi-nation of the deadbanded magnitude from the instantaneous magnitude.Note that the ANALOG IN 1 MIN and ANALOG IN 1 MAX settings are stored as IEEE 754 / IEC 60559 floating pointnumbers. Because of the large range of these settings, not all values can be stored. Some values may be roundedto the closest possible floating point number.The GGIO5 integer configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO5 ANALOG CONFIGURATIONThe GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that ofGGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point.It is intended that clients use GGIO5 to access generic integer values from the B30. Additional settings are provided toallow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to theGGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.• GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger value to drive each GGIO5 integer status value(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value. GGIO4 ANALOG 1 MEASURED VALUEANALOG IN 1 VALUE:OffRange: any FlexAnalog valueMESSAGE ANALOG IN 1 DB:0.000Range: 0.000 to 100.000 in steps of 0.001MESSAGE ANALOG IN 1 MIN:0.000Range: –1000000000.000 to 1000000000.000 in stepsof 0.001MESSAGE ANALOG IN 1 MAX:0.000Range: –1000000000.000 to 1000000000.000 in stepsof 0.001 GGIO5 UINTEGER CONFIGURATIONGGIO5 UINT In 1:OffRange: Off, any FlexInteger parameterMESSAGE GGIO5 UINT In 2:OffRange: Off, any FlexInteger parameterMESSAGE GGIO5 UINT In 3:OffRange: Off, any FlexInteger parameter↓MESSAGE GGIO5 UINT 1n 16:OffRange: Off, any FlexInteger parameterNOTE