5-12 B90 Low Impedance Bus Differential System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS55.2.5 COMMUNICATIONSa) MAIN MENUPATH: SETTINGS PRODUCT SETUP COMMUNICATIONSb) SERIAL PORTSPATH: SETTINGS PRODUCT SETUP COMMUNICATIONS SERIAL PORTSThe B90 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended forlocal use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernetor RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important thatthese parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any ofthese ports may be connected to a computer running EnerVista UR Setup. This software can download and upload settingfiles, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-nected to a DCS, PLC or PC using the RS485 ports. COMMUNICATIONS SERIAL PORTS See below.MESSAGE NETWORK See page 5–13.MESSAGE MODBUS PROTOCOL See page 5–13.MESSAGE DNP PROTOCOL See page 5–14.MESSAGE DNP / IEC104 POINT LISTS See page 5–17.MESSAGE IEC 61850 PROTOCOL See page 5–18.MESSAGE WEB SERVER HTTP PROTOCOL See page 5–27.MESSAGE TFTP PROTOCOL See page 5–28.MESSAGE IEC 60870-5-104 PROTOCOL See page 5–28.MESSAGE SNTP PROTOCOL See page 5–29. SERIAL PORTSRS485 COM1 BAUDRATE: 19200Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,28800, 33600, 38400, 57600, 115200. Onlyactive if CPU Type E is ordered.MESSAGE RS485 COM1 PARITY:NoneRange: None, Odd, EvenOnly active if CPU Type E is orderedMESSAGE RS485 COM1 RESPONSEMIN TIME: 0 msRange: 0 to 1000 ms in steps of 10Only active if CPU Type E is orderedMESSAGE RS485 COM2 BAUDRATE: 19200Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,28800, 33600, 38400, 57600, 115200MESSAGE RS485 COM2 PARITY:NoneRange: None, Odd, EvenMESSAGE RS485 COM2 RESPONSEMIN TIME: 0 msRange: 0 to 1000 ms in steps of 10