5-36 B90 Low Impedance Bus Differential System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5c) TRIP AND ALARM LEDSPATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS TRIP & ALARM LEDSThe trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Eachindicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.d) USER-PROGRAMMABLE LED 1(48)PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LED 1(48)There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-nate when the selected FlexLogic™ operand is in the logic 1 state.For the standard faceplate, the LEDs are located as follows.• LED Panel 2: user-programmable LEDs 1 through 24• LED Panel 3: user programmable LEDs 25 through 48For the enhanced faceplate, the LEDs are located as follows.• LED column 2: user-programmable LEDs 1 through 12• LED column 3: user-programmable LEDs 13 through 24• LED column 4: user-programmable LEDs 25 through 36• LED column 5: user-programmable LEDs 37 through 48Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the LED 1 TYPE setting is“Self-Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the LED 1 TYPE set-ting is “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-munications channel, or from any programmed operand, even if the LED operand state de-asserts. TRIP & ALARM LEDSTRIP LED INPUT:OffRange: FlexLogic™ operandMESSAGE ALARM LED INPUT:OffRange: FlexLogic™ operand USER-PROGRAMMABLE LED 1LED 1 OPERAND:OffRange: FlexLogic™ operandMESSAGE LED 1 TYPE:Self-ResetRange: Self-Reset, LatchedTable 5–3: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDSSETTING PARAMETER SETTING PARAMETERLED 1 operand SETTING GROUP ACT 1 LED 13 operand OffLED 2 operand SETTING GROUP ACT 2 LED 14 operand OffLED 3 operand SETTING GROUP ACT 3 LED 15 operand OffLED 4 operand SETTING GROUP ACT 4 LED 16 operand OffLED 5 operand SETTING GROUP ACT 5 LED 17 operand OffLED 6 operand SETTING GROUP ACT 6 LED 18 operand OffLED 7 operand Off LED 19 operand OffLED 8 operand Off LED 20 operand OffLED 9 operand Off LED 21 operand OffLED 10 operand Off LED 22 operand OffLED 11 operand Off LED 23 operand OffLED 12 operand Off LED 24 operand Off