GE Multilin B90 Low Impedance Bus Differential System 5-855 SETTINGS 5.5 GROUPED ELEMENTS55.5.4 BREAKER FAILUREPATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) BREAKER FAILURE 1(24) BREAKER FAILURE BREAKER FAILURE CURRENT SUPV 1MESSAGE BF1 CURRENT SUPVFUNCTION: DisabledRange: Disabled, EnabledMESSAGE BF1 CT:F1Range: Available current channelsMESSAGE BF1 AMP SUPVPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 AMP HISETPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 AMP LOSETPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001 BREAKER FAILURE 1MESSAGE BF1 FUNCTION:DisabledRange: Disabled, EnabledMESSAGE BF1 INITIATE:OffRange: FlexLogic™ operandMESSAGE BF1 USE AMP SUPV:YesRange: Yes, NoMESSAGE BF1 USE SEAL-IN:YesRange: Yes, NoMESSAGE BF1 AMP SUPV OP A:OffRange: FlexLogic™ operandMESSAGE BF1 AMP SUPV OP B:OffRange: FlexLogic™ operandMESSAGE BF1 AMP SUPV OP C:OffRange: FlexLogic™ operandMESSAGE BF1 USE TIMER 1:YesRange: Yes, NoMESSAGE BF1 TIMER 1 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 2:YesRange: Yes, NoMESSAGE BF1 TIMER 2 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 3:YesRange: Yes, No