GE Multilin B90 Low Impedance Bus Differential System 5-1275 SETTINGS 5.7 INPUTS/OUTPUTS5DIRECT OUT 2 OPERAND: " HYB POTT TX1 "DIRECT OUT 3 OPERAND: " DIRECT INPUT 5 " (forward a message from 1 to 3)DIRECT OUT 4 OPERAND: " DIRECT INPUT 6 " (forward a message from 3 to 1)Signal flow between the three IEDs is shown in the figure below:Figure 5–65: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, directinputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip (HYB POTTRX1 setting).5.7.11 IEC 61850 GOOSE ANALOGSPATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE ANALOGS GOOSE ANALOG INPUT 1(16)The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-seriesdevices. The following settings are available for each GOOSE analog input.• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offlineand the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floatingpoint number. Because of the large range of this setting, not all possible values can be stored. Some values may berounded to the closest possible floating point number.• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE analog input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actualvalues display of the corresponding GOOSE analog input value.GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user toconfigure GOOSE Analog, so that it can be used in a FlexElement.GOOSE Analogs that represent current, voltage, power, frequency, angles, or power factor can be used in a FlexEle-ment. The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz,deg, and no text (blank setting) for power factor. GOOSE ANALOG INPUT 1ANALOG 1 DEFAULT:1000.000Range: –1000000.000 to 1000000.000 in steps of 0.001MESSAGE ANALOG 1 DEFAULTMODE: Default ValueRange: Default Value, Last KnownMESSAGE GOOSE ANALOG 1UNITS:Range: up to 4 alphanumeric charactersMESSAGE GOOSE ANALOG 1 PU:1.000Range: 0.000 to 1000000000.000 in steps of 0.001842717A1.CDRUR IED 3UR IED 2UR IED 1DIRECT OUT 2 = HYB POTT TX1DIRECT INPUT 5DIRECT INPUT 6DIRECT OUT 2 = HYB POTT TX1DIRECT INPUT 5DIRECT INPUT 6DIRECT OUT 2 = HYB POTT TX1DIRECT INPUT 6DIRECT OUT 4 = DIRECT INPUT 6DIRECT OUT 3 = DIRECT INPUT 5DIRECT INPUT 5