GE Multilin C70 Capacitor Bank Protection and Control System 5-195 SETTINGS 5.2 PRODUCT SETUP5The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.The “login setting” in this menu is similar to the login setting described in PATH: SETTINGS > PRODUCT SETUP > SECU-RITY except for the factory role.Passwords are stored in text format. No encryption is applied.Notes:• In Device Authentication mode, the Observer role does not have a password associated with it. In Server Authentica-tion mode the Observer role requires a password.• The default password is “ChangeMe1#”.• Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.• In CyberSentry, password encryption is not supported.Session SettingsPATH: SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGSThe following session settings are available.• SESSION LOCKOUT: This setting specifies the number of failed authentications (the default is three and the maxi-mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero meanslockout is disabled.• SESSION LOCKOUT PERIOD: This setting specifies the period of time in minutes of a lockout period (the default isthree and the maximum is 9999). A value of 0 means that there is no lockout period.Restore DefaultsPATH: SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS• LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. AnAdministrator role is used to change this setting and a Supervisor role (if not disabled) approves it. SESSION SETTINGSSESSION LOCKOUT:3Range: 0 to 99MESSAGE SESSION LOCKOUTPERIOD: 3 minRange: 0 to 9999 minutes RESTORE DEFAULTSLOAD FACTORYDEFAULTS: NoRange: Yes, NoNOTE