GE Multilin C70 Capacitor Bank Protection and Control System B-27APPENDIX B B.4 MEMORY MAPPINGB3B24 ...Repeated for Field Shared Input 53B2D ...Repeated for Field Shared Input 63B36 ...Repeated for Field Shared Input 73B3F ...Repeated for Field Shared Input 83B48 ...Repeated for Field Shared Input 93B51 ...Repeated for Field Shared Input 103B5A ...Repeated for Field Shared Input 113B63 ...Repeated for Field Shared Input 123B6C ...Repeated for Field Shared Input 133B75 ...Repeated for Field Shared Input 143B7E ...Repeated for Field Shared Input 153B87 ...Repeated for Field Shared Input 16Field Unit Contact Outputs (Read/Write Setting) (8 modules)3B90 Field Contact Output 1 ID (6 items) --- --- --- F205 "FCO U /OUT"3BB4 Field Output 1 Operate (6 items) 0 to 4294967295 --- 1 F300 03BC0 Field Output 1 Seal In (6 items) 0 to 4294967295 --- 1 F300 03BCC Field Output 1 Events (6 items) 0 to 1 --- 1 F102 1 (Enabled)3BD2 ...Repeated for Field Contact Output 23C14 ...Repeated for Field Contact Output 33C56 ...Repeated for Field Contact Output 43C98 ...Repeated for Field Contact Output 53CDA ...Repeated for Field Contact Output 63D1C ...Repeated for Field Contact Output 73D5E ...Repeated for Field Contact Output 8Field Unit Latching Outputs (Read/Write Setting) (8 modules)3DC7 Field Latching Output 1 ID 0 to 1 --- 1 F205 "FLO Ux /LO"3DCD Field Latching Output 1 Open 0 to 4294967295 --- 1 F300 03DCF Field Latching Output 1 Close 0 to 4294967295 --- 1 F300 03DD1 Field Latching Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)3DD2 Field Latching Output 1 Reserved (2 items) 0 to 1 --- 1 F001 03DD4 ...Repeated for Field Latching Output 23DE1 ...Repeated for Field Latching Output 33DEE ...Repeated for Field Latching Output 43DFB ...Repeated for Field Latching Output 53E08 ...Repeated for Field Latching Output 63E15 ...Repeated for Field Latching Output 73E22 ...Repeated for Field Latching Output 8Field Unit Shared Outputs (Read/Write Setting) (16 modules)3E30 Field Shared Output 1 ID 0 to 65535 --- 1 F205 "SO 1"3E36 Field Shared Output 1 Operate 0 to 4294967295 --- 1 F300 03E38 Field Shared Output 1 Unit Dest 1 0 to 8 --- 1 F256 0 (None)3E39 Field Shared Output 1 Channel Dest 1 1 to 15 --- 1 F001 13E3A Field Shared Output 1 Unit Dest 2 0 to 8 --- 1 F256 0 (None)3E3B Field Shared Output 1 Channel Dest 2 1 to 15 --- 1 F001 13E3C Field Shared Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)3E3D ...Repeated for Field Shared Output 23E4A ...Repeated for Field Shared Output 33E57 ...Repeated for Field Shared Output 43E64 ...Repeated for Field Shared Output 53E71 ...Repeated for Field Shared Output 63E7E ...Repeated for Field Shared Output 73E8B ...Repeated for Field Shared Output 83E98 ...Repeated for Field Shared Output 93EA5 ...Repeated for Field Shared Output 10Table B–10: MODBUS MEMORY MAP (Sheet 19 of 65)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT