GE Multilin C70 Capacitor Bank Protection and Control System 5-1595 SETTINGS 5.6 GROUPED ELEMENTS5d) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P, IEC PIOC)PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT PHASE IOC 1(12)The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as adefinite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan-taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A).Figure 5–60: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC PHASE IOC1PHASE IOC1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE PHASE IOC1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6MESSAGE PHASE IOC1PICKUP: 1.000 puRange: 0.000 to 30.000 pu in steps of 0.001MESSAGE PHASE IOC1 PICKUPDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 RESETDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 BLOCK A:OffRange: FlexLogic operandMESSAGE PHASE IOC1 BLOCK B:OffRange: FlexLogic operandMESSAGE PHASE IOC1 BLOCK C:OffRange: FlexLogic operandMESSAGE PHASE IOC1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE PHASE IOC1EVENTS: DisabledRange: Disabled, Enabled827033A8.CDRANDANDANDSETTING1 = EnabledFunctionSETTING= IASource= ICSETTINGS= OffBlock A= OffBlock B= OffBlock CSETTINGPickupRUNIA > PickupRUNIB > PickupRUNIC > Pickup= IBSETTINGSPickup DelayT PKPT RSTReset DelayT PKPT RSTT PKPT RSTORFLEXLOGIC OPERANDSPHASE IOC1 A PKPPHASE IOC1 A DPOPHASE IOC1 B PKPPHASE IOC1 B DPOPHASE IOC1 C PKPPHASE IOC1 C DPOPHASE IOC1 PKPFLEXLOGIC OPERANDPHASE IOC1 A OPPHASE IOC1 B OPPHASE IOC1 C OPFLEXLOGIC OPERANDSOR PHASE IOC1 OPFLEXLOGIC OPERANDAND PHASE IOC1 DPOFLEXLOGIC OPERAND