GE Multilin C70 Capacitor Bank Protection and Control System 5-1635 SETTINGS 5.6 GROUPED ELEMENTS5f) PHASE CURRENT UNBALANCE (ANSI 60P, IEC PVCB/PTOC)PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT PHASE CURRENT UNBALANCE 1(3) PHASE CURRENT UNBALANCE 1CUR UNBALCE 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE CUR UNBALCE 1 DIFSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6MESSAGE CUR UNBALCE 1 BANKSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6MESSAGE CUR UNBALCE 1 INHNTFACTOR A: 0.0000Range: –0.1000 to 0.1000 in steps of 0.0001MESSAGE CUR UNBALCE 1 INHNTFACTOR B: 0.0000Range: –0.1000 to 0.1000 in steps of 0.0001MESSAGE CUR UNBALCE 1 INHNTFACTOR C: 0.0000Range: –0.1000 to 0.1000 in steps of 0.0001MESSAGE CUR UNBALCE 1 STG 1APICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 2APICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 3APICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 4APICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 1BPICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 2BPICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 3BPICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 4BPICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 1CPICKUP: 0.020 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 2CPICKUP: 0.030 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 3CPICKUP: 0.040 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 4CPICKUP: 0.050 puRange: 0.001 to 5.000 pu in steps of 0.001MESSAGE CUR UNBALCE 1 STG 1PKP DELAY: 30.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE CUR UNBALCE 1 STG 2PKP DELAY: 10.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE CUR UNBALCE 1 STG 3PKP DELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01