GE Multilin C70 Capacitor Bank Protection and Control System B-35APPENDIX B B.4 MEMORY MAPPINGB4CA0 ...Repeated for User-Definable Display 64CC0 ...Repeated for User-Definable Display 74CE0 ...Repeated for User-Definable Display 84D00 ...Repeated for User-Definable Display 94D20 ...Repeated for User-Definable Display 104D40 ...Repeated for User-Definable Display 114D60 ...Repeated for User-Definable Display 124D80 ...Repeated for User-Definable Display 134DA0 ...Repeated for User-Definable Display 144DC0 ...Repeated for User-Definable Display 154DE0 ...Repeated for User-Definable Display 16Field Unit Raw Data Actuals (Read Only) (8 modules)4E00 Raw Field Data AC1 Mag 0 to 0.001 A 0.001 F003 04E02 Raw Field Data AC1 Angle 0 to 0.1 degree 0.1 F002 04E03 Raw Field Data AC2 Mag 0 to 0.001 A 0.001 F003 04E05 Raw Field Data AC2 Angle 0 to 0.1 degree 0.1 F002 04E06 Raw Field Data AC3 Mag 0 to 0.001 A 0.001 F003 04E08 Raw Field Data AC3 Angle 0 to 0.01 degree 0.1 F002 04E09 Raw Field Data AC4 Mag 0 to 0.001 A 0.001 F003 04E0B Raw Field Data AC4 Angle 0 to 0.01 degree 0.1 F002 04E0C Raw Field Data AC5 Mag 0 to 0.001 A/V 0.001 F003 04E0E Raw Field Data AC5 Angle 0 to 0.01 degree 0.1 F002 04E0F Raw Field Data AC6 Mag 0 to 0.001 A/V 0.001 F003 04E11 Raw Field Data AC6 Angle 0 to 0.01 degree 0.1 F002 04E12 Raw Field Data AC7 Mag 0 to 0.001 A/V 0.001 F003 04E14 Raw Field Data AC7 Angle 0 to 0.01 degree 0.1 F002 04E15 Raw Field Data AC8 Mag 0 to 0.001 A/V 0.001 F003 04E17 Raw Field Data AC8 Angle 0 to 0.01 degree 0.1 F002 04E18 Raw Field Data DC1 0 to 0.001 V 0.001 F002 04E19 Raw Field Data DC2 0 to 0.001 V 0.001 F002 04E1A Raw Field Data DC3 0 to 0.001 V 0.001 F002 04E1B Raw Field Data FCI States (2 items) 0 to 1 --- 1 F500 04E1D Raw Field Data SI States 0 to 1 --- 1 F500 04E1E Raw Field Data SI Test States 0 to 1 --- 1 F500 04E1F Raw Field Data Brick ADC Temperature 0 to 1 degree 1 F002 04E20 Raw Field Data Brick Transceiver Temperature 0 to 1 degree 1 F002 04E21 Raw Field Data Brick Transceiver Voltage 0 to 0.01 V 0.01 F001 04E22 Raw Field Data Brick Transceiver Current 0 to 1 mA 1 F001 04E23 Raw Field Data Brick Tx Power 0 to 0.1 dBm 0.1 F002 04E24 Raw Field Data Brick Rx Power 0 to 0.1 dBm 0.1 F002 04E25 Raw Field Data Brick Diagnostics (2 items) 0 to 65535 --- 1 F500 04E27 Raw Field Data Local Transceiver Temperature 0 to 1 degree 1 F002 04E28 Raw Field Data Local Transceiver Voltage 0 to 0.01 V 0.01 F001 04E29 Raw Field Data Local Transceiver Current 0 to 1 mA 1 F001 04E2A Raw Field Data Local Tx Power 0 to 0.1 dBm 0.1 F002 04E2B Raw Field Data Local Rx Power 0 to 0.1 dBm 0.1 F002 04E2C Repeated for Field Unit 24E58 Repeated for Field Unit 34E84 Repeated for Field Unit 44E80 Repeated for Field Unit 54EDC Repeated for Field Unit 64F08 Repeated for Field Unit 74F34 Repeated for Field Unit 8Table B–10: MODBUS MEMORY MAP (Sheet 27 of 65)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT