GE Multilin C70 Capacitor Bank Protection and Control System 5-775 SETTINGS 5.2 PRODUCT SETUP5See the figure in the Setting Groups section in the Control Elements section later in this chapter for an example of groupactivation.5.2.11 USER-PROGRAMMABLE SELF TESTSPATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE SELF TESTSAll major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Mostof the minor alarms can be disabled if desired.When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display targetmessages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7 forinformation on major and minor self-test alarms. USER-PROGRAMMABLE SELF TESTSDIRECT RING BREAKFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equipped withDirect Input/Output module.MESSAGE DIRECT DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equipped withDirect Input/Output module.MESSAGE REMOTE DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE FIRST ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE SEC. ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE THIRD ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE BATTERY FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE SNTP FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE IRIG-B FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE PTP FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE SFP MODULE FAILFUNCTION: DisabledRange: Disabled, Enabled.