5-112 C70 Capacitor Bank Protection and Control System GE Multilin5.5 FLEXLOGIC 5 SETTINGS5The operands available for this relay are listed alphabetically by types in the following table.Table 5–12: C70 FLEXLOGIC OPERANDS (Sheet 1 of 9)OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTIONCONTROLPUSHBUTTONSCONTROL PUSHBTN 1 ONCONTROL PUSHBTN 2 ONCONTROL PUSHBTN 3 ONCONTROL PUSHBTN 4 ONCONTROL PUSHBTN 5 ONCONTROL PUSHBTN 6 ONCONTROL PUSHBTN 7 ONControl pushbutton 1 is being pressedControl pushbutton 2 is being pressedControl pushbutton 3 is being pressedControl pushbutton 4 is being pressedControl pushbutton 5 is being pressedControl pushbutton 6 is being pressedControl pushbutton 7 is being pressedDIRECT DEVICES DIRECT DEVICE 1OnDIRECT DEVICE 16OnDIRECT DEVICE 1OffDIRECT DEVICE 16OffFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1Flag is set, logic=1DIRECT INPUT/OUTPUTCHANNELMONITORINGDIR IO CH1 CRC ALARMDIR IO CH2 CRC ALARMDIR IO CH1 UNRET ALMDIR IO CH2 UNRET ALMThe rate of direct input messages received on channel 1 and failing the CRCexceeded the user-specified level.The rate of direct input messages received on channel 2 and failing the CRCexceeded the user-specified level.The rate of returned direct input/output messages on channel 1 exceeded theuser-specified level (ring configurations only).The rate of returned direct input/output messages on channel 2 exceeded theuser-specified level (ring configurations only).ELEMENT:AuxiliaryovervoltageAUX OV1 PKPAUX OV1 DPOAUX OV1 OPAuxiliary overvoltage element has picked upAuxiliary overvoltage element has dropped outAuxiliary overvoltage element has operatedAUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1ELEMENT:Automatic voltageregulatorAVR 1 CLOSE PKPAVR 1 CLOSE OPAVR 1 CLOSE DPOAVR 1 OPEN PKPAVR 1 OPEN OPAVR 1 OPEN DPOAutomatic voltage regulator 1 picked up; close command pendingAutomatic voltage regulator 1 issued a close commandClose command of automatic voltage regulator 1 dropped outAutomatic voltage regulator 1 picked up; open command pendingAutomatic voltage regulator 1 issued an open commandOpen command of automatic voltage regulator 1 dropped outAVR 2 to AVR 3 Same set of operands as shown for AVR 1ELEMENT:Bank phaseovervoltageBANK OV 1 STG 1A PKPBANK OV 1 STG 1B PKPBANK OV 1 STG 1C PKPBANK OV 1 STG 2A PKPBANK OV 1 STG 2B PKPBANK OV 1 STG 2C PKPBANK OV 1 STG 3A PKPBANK OV 1 STG 3B PKPBANK OV 1 STG 3C PKPBANK OV 1 STG 4A PKPBANK OV 1 STG 4B PKPBANK OV 1 STG 4C PKPBANK OV 1 PKP ABANK OV 1 PKP BBANK OV 1 PKP CBANK OV 1 PKPBANK OV 1 DPOBANK OV 1 STG 1A OPBANK OV 1 STG 1B OPBANK OV 1 STG 1C OPBANK OV 1 STG 2A OPBANK OV 1 STG 2B OPBANK OV 1 STG 2C OPBANK OV 1 STG 3A OPBANK OV 1 STG 3B OPBANK OV 1 STG 3C OPBANK OV 1 STG 4A OPBANK OV 1 STG 4B OPBANK OV 1 STG 4C OPBANK OV 1 OP ABANK OV 1 OP BBANK OV 1 OP CBANK OV 1 OPBank overvoltage element 1 picked up in phase A of stage 1Bank overvoltage element 1 picked up in phase B of stage 1Bank overvoltage element 1 picked up in phase C of stage 1Bank overvoltage element 1 picked up in phase A of stage 2Bank overvoltage element 1 picked up in phase B of stage 2Bank overvoltage element 1 picked up in phase C of stage 2Bank overvoltage element 1 picked up in phase A of stage 3Bank overvoltage element 1 picked up in phase B of stage 3Bank overvoltage element 1 picked up in phase C of stage 3Bank overvoltage element 1 picked up in phase A of stage 4Bank overvoltage element 1 picked up in phase B of stage 4Bank overvoltage element 1 picked up in phase C of stage 4Bank overvoltage element 1 picked up in phase ABank overvoltage element 1 picked up in phase BBank overvoltage element 1 picked up in phase CBank overvoltage element 1 picked upBank overvoltage element 1 dropped outBank overvoltage element 1 operated in phase A of stage 1Bank overvoltage element 1 operated in phase B of stage 1Bank overvoltage element 1 operated in phase C of stage 1Bank overvoltage element 1 operated in phase A of stage 2Bank overvoltage element 1 operated in phase B of stage 2Bank overvoltage element 1 operated in phase C of stage 2Bank overvoltage element 1 operated in phase A of stage 3Bank overvoltage element 1 operated in phase B of stage 3Bank overvoltage element 1 operated in phase C of stage 3Bank overvoltage element 1 operated in phase A of stage 4Bank overvoltage element 1 operated in phase B of stage 4Bank overvoltage element 1 operated in phase C of stage 4Bank overvoltage element 1 operated in phase ABank overvoltage element 1 operated in phase BBank overvoltage element 1 operated in phase CBank overvoltage element 1 operatedBANK OV 2 to BANK OV 3 Same set of operands as shown for BANK OV 1