GE Multilin C70 Capacitor Bank Protection and Control System B-29APPENDIX B B.4 MEMORY MAPPINGB4508 ...Repeated for VT Bank 24510 ...Repeated for VT Bank 34518 ...Repeated for VT Bank 44520 ...Repeated for VT Bank 54528 ...Repeated for VT Bank 6Source Settings (Read/Write Setting) (6 modules)4580 Source 1 Name 0 to 1 --- --- F206 “SRC 1"4583 Source 1 Phase CT 0 to 63 --- 1 F400 04584 Source 1 Ground CT 0 to 63 --- 1 F400 04585 Source 1 Phase VT 0 to 63 --- 1 F400 04586 Source 1 Auxiliary VT 0 to 63 --- 1 F400 04587 ...Repeated for Source 2458E ...Repeated for Source 34595 ...Repeated for Source 4459C ...Repeated for Source 545A3 ...Repeated for Source 6Power System (Read/Write Setting)4600 Nominal Frequency 25 to 60 Hz 1 F001 604601 Phase Rotation 0 to 1 --- 1 F106 0 (ABC)4602 Frequency And Phase Reference 0 to 5 --- 1 F167 0 (SRC 1)4603 Frequency Tracking Function 0 to 1 --- 1 F102 1 (Enabled)Breaker control (read/write settings)47D0 Breaker 1 function 0 to 1 --- 1 F102 0 (Disabled)47D1 Breaker 1 name --- --- --- F206 “Bkr 1"47D4 Breaker 1 mode 0 to 1 --- 1 F157 0 (3-Pole)47D5 Breaker 1 open 0 to 4294967295 --- 1 F300 047D7 Breaker 1 close 0 to 4294967295 --- 1 F300 047D9 Breaker 1 phase A / three-pole closed 0 to 4294967295 --- 1 F300 047DB Breaker 1 phase B closed 0 to 4294967295 --- 1 F300 047DD Breaker 1 phase C closed 0 to 4294967295 --- 1 F300 047DF Breaker 1 external alarm 0 to 4294967295 --- 1 F300 047E1 Breaker 1 alarm delay 0 to 65.535 s 0.001 F003 047E3 Breaker 1 pushbutton control 0 to 1 --- 1 F102 0 (Disabled)47E4 Breaker 1 manual close recall time 0 to 4294967295 s 0.001 F003 047E6 Breaker 1 out of service 0 to 4294967295 --- 1 F300 047E8 Breaker 1 block open 0 to 4294967295 --- 1 F300 047EA Breaker 1 block close 0 to 4294967295 --- 1 F300 047EC Breaker 1 phase A / three-pole opened 0 to 4294967295 --- 1 F300 047EE Breaker 1 phase B opened 0 to 4294967295 --- 1 F300 047F0 Breaker 1 phase C opened 0 to 4294967295 --- 1 F300 047F2 Breaker 1 operate time 0 to 65.535 s 0.001 F001 7047F3 Breaker 1 events 0 to 1 --- 1 F102 0 (Disabled)47F4 Reserved 0 to 65535 s 1 F001 047F5 ...Repeated for breaker 2481A ...Repeated for breaker 3483F ...Repeated for breaker 44864 ...Repeated for breaker 54889 ...Repeated for breaker 6FlexCurve A (Read/Write Setting)4910 FlexCurve A (120 items) 0 to 655535 ms 1 F011 0FlexCurve B (Read/Write Setting)4988 FlexCurve B (120 items) 0 to 655535 ms 1 F011 0Modbus User Map (Read/Write Setting)4A00 Modbus Address Settings for User Map (256 items) 0 to 65535 --- 1 F001 0Table B–9: MODBUS MEMORY MAP (Sheet 22 of 61)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT